송전케이블 삼상단락 실증시험을 통한 전자력 대책방안 연구

The Study on Countermeasures of Electromagnetic Force by Three Phase Short-Circuit Test of Underground Transmission Cable

  • 강지원 (한전 전력연구원) ;
  • 박흥석 (한전 전력연구원) ;
  • 윤종건 (한전 송변전선건설처 송전건설팀) ;
  • 김양상 (한전 송변전운영처 송전운영팀) ;
  • 홍동석 (대한전선 기술연구소) ;
  • 장우석 (대한전선 시스템엔지니어링팀)
  • 발행 : 2009.12.01

초록

Even though underground transmission cable is an essential transmission method to supply stable power for downtown and population center, the interaction of electromagnetic force by fault current is very large comparing to overhead transmission line due to restricted installation space such as tunnel, and close consideration is required for it. This paper presents countermeasures to reduce and release the effect of electromagnetic force with rope binding and installation of spacer and describes its efficacy through three phase short-circuit test, which will be utilized as basic materials for improvement and development of cleat, hanger, etc. to reduce and release effect of electromagnetic force in the future.

키워드

참고문헌

  1. '지중송전계통의 접지기술 정립에 관한 연구', 한국전력공사 전력연구원 최종보고서, 1998.01
  2. Charles A Damell, 'Cable Cleat-A Global Technique to Protect Three-Phase Single Conductor Cables during Short-Circuits' IEEE Transmission on Power Delivery, pp.143-150, 2004
  3. F. Donazzi, R. Gaspari, and et. aI., 'Research on the Performance of 400kV Extruded Cable System under Short Circuit Conditions', CIGRE 1996: 21-205
  4. 한국전력공사 송변전건설처, ‘지중송전 케이블시스템’, 2002. 12
  5. 장태인, 박흥석, 강지원, 윤형희, 홍동석, '고장전류에 의한 154kV 지중케이블의 작용 전자력 해석', 대한전기학회 추계학술대회 논문집, 2008. 11
  6. 전기협동연구 제 61권 제 1호, 'CV 케이블 선로에 대한 공사기술의 현상과 향후 전망
  7. 한전 구매시방서, ‘154kV 알루미늄피 유입케이블 및 부속재’, 2002.01
  8. ‘변전소 근단공장시 고장전류에 의한 154kV 지중송전 케이블 영향분석 및 방지대책’, 한국전력공사 전력연구원 최종보고서, 2009.07