Accelerating Aging of Transmission Line Porcelain Suspension Insulators by Autoclaving

  • 발행 : 2008.08.31

초록

Porcelain suspension insulators aged for 1, 5 and 10 years on Korean transmission lines and new insulators are tested for autoclave expansion. The compressive strength of the insulators aged in an autoclave with conditions of $250\;^{\circ}C$ and at 20 atm for 30 minutes, was about $7.6\;kgf/mm^2$, which is close to that measured on insulators aged for 10 years in the field. From simulation results, the cement displacement changed linearly with temperature. At a temperature of $200\;^{\circ}C$, the shear stress was approximately $7\;kgf/mm^2$; a stress that is brought about by a 0.07 % expansion of the cement. It is evident that the cement would fracture at a 0.07 % expansion, because the cement has about 7 to $9\;kgf/mm^2$ flexure strength. A turning point in the shear stress with mechanical load occurred at 0.02 % cement expansion. From an analysis of the porcelain body it is shown that there is sufficient margin of strength to guard against fracture of the porcelain body even for a cement expansion more than 0.12 %.

키워드

참고문헌

  1. S. W. Han and H. G. Cho, "A study on electrical and mechanical simulation for designing porcelain insulators with high strength", ICEE 2002 Proceeding, Vol. 13, p. 1191, 2002
  2. E. A. Cherney, "Cement growth failure of porcelain suspension insulators", IEEE PAS, Vol. PAS-102, No. 8, p. 2765, 1983 https://doi.org/10.1109/TPAS.1983.317959
  3. S. W. Han and H. G. Cho, "Study on performance and aging test of porcelain insulators for transmission line", J. of KIEEME(in Korean), Vol. 16, No. 9, p. 842, 2003 https://doi.org/10.4313/JKEM.2003.16.9.842
  4. J. S. T. Looms, "Insulators for high voltages", Chpter 2, IEE Power Engineering Series 7, Peter Peregrinus Ltd, 1988
  5. K. Morita, Y. Susuki, and H. Nozaki, "Study on long term reliability of suspension insulators", TIEE Japan, Vol. 117-B, No. 12, p. 1529, 1997
  6. J. Bellerive, "Performance of porcelain insulator, forty years experiences at Hydro Quebec", CEA Paper, March, 1990