웨이브릿 기법을 이용한 리커시브 실시간 고장점 표정 시스템 연구

Recursive Real Time Fault Locator with Wavelet Method

  • 이성우 (한전 전력연구원 책임연구원) ;
  • 하복남 (한전 전력연구원 수석연구원)
  • 발행 : 2008.09.01

초록

This paper presents a discrete wavelet analysis based algorithm to address the fault impedance calculation under transient state in radial power distribution networks. The fault impedances have been derived under different fault conditions. Furthermore, a recursive fault distance estimation method is proposed utilizing the measured fault impedance and power line parameters. The proposed scheme can resolve the errors caused by the non-homogeneous power lines, the presence of lateral loads since, the fault impedance will always be updated with the recursive form. For the verification of the proposed scheme, a filed test has been peformed with varying fault resistances in the 22.9(kV) radial system. Power meters and fault locators were installed at the substation. It was figured out that the performance of the discrete wavelet and the recursive scheme are very good even for high fault resistance condition.

키워드

참고문헌

  1. WELFONDER, T. et al, Location Strategies and Evaluation of Detection Algorithms for Earth Faults in Compensated MV Distribution Systems, IEEE Transactions on Power Delivery 15 No. 4, pp. 1121-1128, 2000 https://doi.org/10.1109/61.891492
  2. D. Novosel, D. Hart, E. Udren and J. Garitty, ""Unsynchronized two-terminal fault location estimation"", IEEE Trans. on Power Delivery, Vol. 11. No. 1, pp. 130-138, Jan, 1996 https://doi.org/10.1109/61.484009
  3. Girgis, d. Hart, W. Peterson, ""A new fault location technique for two and three terminal lines"", IEEE Trans. on Power Delivery, Vol. 7, No. 1, pp. 98-107, Jan, 1992 https://doi.org/10.1109/61.108895
  4. J. Jiang, J. Yang, Y. Lin, C. Liu and J. Ma, ""An adaptive PMU based fault detection/location technique for transmission lines. P. I: Theory and algorithms"", IEEE Trans. on Power Delivery, Vol. 15, No. 2, pp. 486-493, Jan, 2000 https://doi.org/10.1109/61.852973
  5. J. Jiang, J. Yang, Y. Lin, C. Liu and J. Ma, ""An adaptive PMU based fault detection/location technique for transmission lines. P. I: Theory and algorithms"", IEEE Trans. on Power Delivery, Vol. 15, No. 4, pp. 1136-146, Oct, 2000 https://doi.org/10.1109/61.891494
  6. V. Cook, ""Fundamental aspects of fault location algorithms used in distance protection"", IEE Proceedings, Vol. 133 Pt. C, pp. 359-366, 1986
  7. M. S. Sachdev and R. Agarwal, ""A technique for estimating line fault locations from digital impedance relay measurements"", IEEE Trans. on Power Delivery, Vol. 3, No. 1, pp. 121-129, Jan, 1988 https://doi.org/10.1109/61.4237
  8. T. Adu, ""A new Transmission Line Fault Locating System"", IEEE Trans. on Power Delivery, Vol. 16, No. 4, pp. 498-503, Oct, 2001 https://doi.org/10.1109/61.956728
  9. T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura and T. Sakaguchi, ""a new algorithm for EHV/UHV transmission lines: Part I-Fourier transform method"", IEEE Trans. on Power Apparatus and Systems, Vol. PAS-100, pp. 1316 1323, 1981 https://doi.org/10.1109/TPAS.1981.316604
  10. T. Takagi, Y. Yamakoshi, M. Yamaura, R. Kondow and T. Matsushima, ""Development of a new type fault locator using the one-terminal voltage and current data"", IEEE Trans. onPower Apparatus and Systems, Vol. PAS-101, pp. 2892-2898, 1982 https://doi.org/10.1109/TPAS.1982.317615
  11. T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, M. Kizilcay and A. Ametani, ""Influence of Fault Arc Characteristics on the Accuracy of digital Fault Locators"", IEEE Trans. On Power Delivery, Vol. 16, No. 2, pp. 195-199, April 2001 https://doi.org/10.1109/61.915482
  12. Hanninen, S., Lehtonen, M. & Hakola, T. 2001. Earth faults and related disturbances in distribution networks. Proceedings of IEEE PES SM2001, July, pp. 673-679
  13. Eberl, G., Hänninen, S., Lehtonen, M. & Schegner, P. 2000. Comparison of artificial neural networks and conventional algorithms in ground fault distance computation. Proceedings of IEEE PES WM2000, Jan. 2000, pp.1991-1996