Experimental Study for Evaporation Heat Transfer and Pressure Drop of R-22 and R-407C in an Inner Diameter of 4.3 mm and 6.4 mm

내경 4.3 mm와 6.4 mm관내 R-22와 R-407C의 증발 열전달과 압력강하에 관한 실험연구

  • Son, Chang-Hyo (School of Mechanical Engineering, Pukyong National University) ;
  • Roh, Geon-Sang (Department of Refrigeration and Air-conditioning Engineering, Tong Myong University)
  • 손창효 (부경대학교 기계공학부) ;
  • 노건상 (동명대학교 냉동공조공학과)
  • Published : 2008.09.30

Abstract

The evaporation heat transfer coefficient and pressure drop of R-22 and R-407C in horizontal copper tubes were investigated experimentally. The main components of therefrigerant loop are a receiver, a compressor, a mass flow meter, a condenser and a double pipe type evaporator (test section). The test section consists of a smooth copper tube of 4.3 mm and 6.4 mm inner diameter. The refrigerant mass fluxes were varied from 100 to $300[kg/m^2s]$ and the saturation temperature of evaporator were 5 [$^{\circ}C$]. The evaporation heat transfer coefficients of R-22 and R-407C rise with the increase in mass flux and vapor quality. The evaporation heat transfer coefficient of R-22 for inner diameter tube of 4.3 mm and 6.4 mm is about $7.3{\sim}47.1%$ and $5.68{\sim}46.6%$ higher than that of R-407C, respectively.

본 연구에서는 내경 4.3 mm와 6.4 mm의 수평동관내 R-22와 R-407C의 증발 열전달과 압력강하를 실험적으로 조사하였다. 냉매 순환루프의 주요구성품은 수액기, 압축기, 질량유량계, 응축기, 이중관식 증발기 (시험부)로 구성된다. 시험부는 내경 4.3 mm와 6.4mm의 평활 동관으로 이루어져 있다. 냉매질량유속은 $100\;kg/m^2s$에서 $300\;kg/m^2s$까지 변화시켰고, 증발기 냉매포화온도는 $5^{\circ}C$이다. R-22와 R-407C의 증발 열전달계수는 질량유속과 증기건도의 증가와 함께 따라 상승한다. 내경 4.3 mm와 6.4mm관내 R-22의 증발 열전달계수가 R-407C에 비해 각각 $7.3{\sim}47.1%$$5.68{\sim}46.6%$ 정도 높다.