DOI QR코드

DOI QR Code

Effect of Water Quality of Cooling Tower on Legionella pneumophila Disinfection Using Ru/Ti Electrode

냉각탑수 수질이 Ru/Ti 전극을 이용한 Legionella pneumophila 소독에 미치는 영향

  • Published : 2008.06.30

Abstract

This study was carried out to evaluate the effect of water quality of cooling tower on Legionella pneumophila disinfection using Ru/Ti electrode. The influences of parameters such as pH, turbidity, $CaCO_3$ and TOC were investigated using laboratory scale batch reactor. Oxidants such as free Cl, $ClO_2,\;H_2O_2\;and\;O_3$ were measured. The results showed that all of the water quality parameters of cooling tower had deteriorated disinfection of Legionella pneumophila. When the turbidity, $CaCO_3$ and TOC was increased, oxidants which was generated during electrolysis was decreased. pH, free Cl, $ClO_2\;and\;H_2O_2$ concentration were decreased with the increase of pH, whereas $O_3$ concentration was increased with the increase of pH. The order of effect of water quality on the disinfection performance for Legionella pneumophila was turbidity > $CaCO_3$ > TOC > pH. To obtain the safety standard (1000 CFU/L), the simultaneous increase current and NaCl dosage was needed.

Keywords

References

  1. 김기영, 2002, 서울시 일부 냉각탑중 레지오넬라의 동정방법별 비교와 영향인자 연구, 박사학위논문, 산업의학과, 한양대학교, 서울
  2. 정종학, 강복수, 김석범, 사공준, 1988, 환경수로부터 Legionella속 세균의 분리, 영남의대학술지, 5(1), 77-82
  3. Field B. S., 1997, Legionella and Legionnaires' disease, Manual of environmental microbiology, ASM Press, 666-675pp
  4. 정현미, 1996, 먹는 물의 수처리 및 수질관리에 관련한 미생물 규제의 국내외 동향 및 개선방안, 국립한경연구원, 기초전문화 과제보고서, 27-40pp
  5. 국립보건원, 2002, 레지오넬라증 예방관리, 23-26pp
  6. Muraca P., Stout J. E., Yu V., 1987, Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system, Appl. Environ. Microbiol., 53(2), 447-453
  7. Oguma K., Katayama H., Ohgaki S., 2004, Photoreactivation of Legionella pneumophila after inactivation by low- or medium-pressure ultraviolet lamp, Wat. Res., 38, 2757-2763 https://doi.org/10.1016/j.watres.2004.03.024
  8. 박영식, 김동석, 2007, 전기화학적 소독에 의한 Legionella pneumophila 불활성화, 한국물환경학회지, 23(5), 613-619
  9. 日本 厚生省 生活衛生局 企劃課, 1993, Legionellosis 防止指針, 財團法人 Building 管理敎育Center
  10. 한국산업규격, 1998, 냉동.공조용 냉각수 수질기준, 한국산업규격 KS M 0077
  11. 김동석, 박영식, 2007, 불용성 전극을 이용한 Rhodamine B의 전기화학적 탈색, 한국물환경학회지, 23(3), 377-384
  12. 권순구, 우준희, 김대수, 어수택, 정연태, 김용훈, 박춘식, 1990, 폐결핵환자에서 호중구의 H$_{2}$O$_{2}$ 형성 및 IgG 수용체의 표현율, 대한내과학회지, 39(5), 613-619
  13. Lin Z., Liu W. J., 2006, Study on factors affecting electrochemical disinfection effect, China Water & Wastewater, 22(23), 70-73
  14. Bergmann M. E. H., Koparal A. S., 2005, Studies on electrochmical disinfectant production using anodes containing RuO$_{2}$, J. Appl. Electrochemistry, 35, 1321-1329 https://doi.org/10.1007/s10800-005-9064-0
  15. Aleboyeh A., Moussa Y., Aleboyeh H., 2005, The effect of operational parameters on UV/H$_{2}$O$_{2}$ decolourisation of Acid Blue 74, Dyes & Pigments, 66, 129-134 https://doi.org/10.1016/j.dyepig.2004.09.008
  16. 이홍구, 이경혁, 박종복, 강준원, 2002, 하수 처리장 방류수를 이용한 고급산화공정 평가, 대한환경공학회지, 24(2), 2175-2182
  17. Jeong J. S., Kim J. Y., Cho M., Choi W. Y., Yonn J. Y., 2007, Inactivation of Escherichia coli in the electrochemical disinfection process using a Pt anode, Chemosphere, 67, 652-659 https://doi.org/10.1016/j.chemosphere.2006.11.035

Cited by

  1. E. coli Disinfection Using a Multi Plasma Reactor vol.39, pp.2, 2013, https://doi.org/10.5668/JEHS.2013.39.2.187