Abstract
The evaporation heat transfer coefficient of $CO_2$ (R-744) in a horizontal tube was investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator (test section). The test section consists of a smooth, horizontal stainless steel tube of inner diameter of 4.57mm. The experiments were conducted at mass flux of 400 to $900kg/m^2s$, saturation temperature of 5 to $20^{\circ}C$, and heat flux of 10 to $40kW/m^2$. The test results showed the heat transfer of $CO_2$ has a greater effect on nucleate boiling more than convective boiling. Mass flux of $CO_2$ does not affect nucleate boiling too much. In comparison with test results and existing correlations, All of the existing correlations for the heat transfer coefficient underestimated the experimental data. However Jung et al.'s correlation showed a good agreement with the experimental data. Therefore, it is necessary to develope accurate predictions determining the evaporation heat transfer coefficient of $CO_2$ in horizontal tubes.
수평관내 $CO_2$의 증발 열전달 계수를 실험적으로 조사하였다. 냉매 순환루프의 주요 구성품은 수액기, 변속냉매 펌프, 질량 유량계, 예열기, 증발기(시험부)로 구성된다. 시험부는 내경 4.57 mm의 수평 평활 스텐레스관이다. 실험은 질량유속 $400{\sim}900kg/m^2s$, 포화온도 $5{\sim}20^{\circ}C$, 열유속 $10{\sim}40kW/m^2$인 조건에서 수행하였다. 실험결과로부터 $CO_2$의 열전달은 대류비등보다는 핵비등에 더 많은 영향을 받는 것을 알 수 있었고, $CO_2$의 질량유속은 핵비등에 많은 영향을 미치지 않는 것으로 나타났다. 실험결과와 종래의 상관식을 비교해 본 결과, 기존의 상관식은 실험데이터를 과소예측하였지만, 정 등의 상관식은 좋은 일치를 보였다. 따라서, 수평관내 $CO_2$의 증발 열전달 계수를 예측할 수 있는 정확한 상관식의 개발이 필요하리라 판단된다.