Abstract

The flux-lock type superconducting fault current limiter(SFCL) can apply the magnetic field into the high-$T_C$ superconducting(HTSC) element by adopting the magnetic field coil in its third winding. To apply the magnetic field into the HTSC element effectively, the capacitor for LC resonance is connected in series with the magnetic field coil. However, the current waveform of third winding for the application of the magnetic field is affected by the LC resonance condition for the frequency of the source voltage and can affect the waveform of the limited fault current. In this paper, the current waveform of the third winding in the flux-lock type SFCL according to LC resonance condition during a fault period was analyzed. From the differential equation for its electrical circuit, the current equation of the third winding was derived and described with the natural frequency and the damping ratio as design parameters. Through the analysis according to the design parameters of the third winding, the waveform of the limited fault current was confirmed to be influenced by the current waveform of the third winding and the design condition for the stable fault current limiting operation of this SFCL was obtained.

Keywords

References

  1. W. Paul and M. Chen, "Superconducting control for surge currents," IEEE Spectrum, vol. 35, pp. 49-54, May 1998
  2. T. Onishi, M. Kawasumi, K.-I. Sakaki, and R. Akimoto, "An experimental study on a fast selfacting magnetic shield type superconducting fault current limiter," IEEE Trans. Appl. Supercond., vol. 12, pp. 868-871, Mar. 2002 https://doi.org/10.1109/TASC.2002.1018538
  3. S. H. Lim, H. S. Choi, D. C. Chung, Y. H. Jeong, Y. H. Han, T. H. Sung, and B. S. Han, "Fault current limiting characteristics of resistive type SFCL using a transformer," IEEE Trans. Appl. Supercond., vol. 15, no. 2, pp. 2055-2058, Jun. 2005 https://doi.org/10.1109/TASC.2005.849450
  4. S. H. Lim, H. S. Choi, and B. S. Han, "The fault current limiting characteristics of a flux-lock type high-TC superconducting fault current limiter using a series resonance," Cryogenics, vol. 44, pp. 249-254, Apr. 2004 https://doi.org/10.1016/j.cryogenics.2003.11.002
  5. S. H. Lim, H. S. Choi, and B. S. Han, "The improved hysteresis characteristics of flux-lock type SFCL using third winding," Phys. C, Vol. 406, pp. 37-45, Jul. 2004 https://doi.org/10.1016/j.physc.2004.02.177
  6. S. H. Lim, T. H. Han, S. W. Yim, H. S. Choi, and B. S. Han, "Current limiting characteristics of a flux-lock type SFCL dependent on fault angles and core saturation," IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 1827-1830, Jun. 2007 https://doi.org/10.1109/TASC.2007.899868
  7. S. H. Lim, H. S. Choi, and B. S. Han, "Fault current limiting characteristics due to winding direction between coil 1 and coil 2 in a flux-lock type SFCL," Phys. C, vol. 416, pp. 34-42, Nov. 2004 https://doi.org/10.1016/j.physc.2004.08.019

Cited by

  1. Recovery behavior based on reclosing operation and a neutral line of three-phase flux-coupling type SFCL vol.471, pp.21-22, 2011, https://doi.org/10.1016/j.physc.2011.05.190
  2. Analysis on fault current limiting and bus-voltage sag suppressing operations of SFCLs using magnetic coupling of two coils according to their application locations in a power distribution system vol.471, pp.21-22, 2011, https://doi.org/10.1016/j.physc.2011.05.194
  3. Analysis on current limiting characteristics of a flux-lock type SFCL with two triggering current levels vol.471, pp.21-22, 2011, https://doi.org/10.1016/j.physc.2011.05.193
  4. Optimal Parameter Selection of Resistive SFCL Applied to a Power System Using Eigenvalue Analysis vol.20, pp.3, 2010, https://doi.org/10.1109/TASC.2010.2041333
  5. Improvement of Recovery Characteristics of a Flux-Lock Type SFCL Using a Superconductor's Trigger vol.20, pp.3, 2010, https://doi.org/10.1109/TASC.2010.2042162
  6. Study on Protection Coordination of a Flux-Lock Type SFCL With Over-Current Relay vol.20, pp.3, 2010, https://doi.org/10.1109/TASC.2010.2045749
  7. Study on Application Method of Superconducting Fault Current Limiter for Protection Coordination of Protective Devices in a Power Distribution System vol.22, pp.3, 2012, https://doi.org/10.1109/TASC.2011.2174551
  8. A Study on the Application of SFCL on 22.9 kV Bus Tie for Parallel Operation of Power Main Transformers in a Power Distribution System vol.60, pp.1, 2011, https://doi.org/10.5370/KIEE.2011.60.1.020
  9. Analysis on Current Limiting Characteristics of Series Connection-type SFCL with Two Magnetically Coupled Circuits Applied into a Simulated Power System vol.26, pp.1, 2013, https://doi.org/10.4313/JKEM.2013.26.1.68
  10. Study on Peak Current Limiting Characteristics of a Flux-Lock Type SFCL Using Its Third Winding vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2093863
  11. Analysis on fault current limiting and recovery characteristics of a flux-lock type SFCL with an isolated transformer vol.484, 2013, https://doi.org/10.1016/j.physc.2012.03.041
  12. Improvement on Current Limiting Characteristics of a Flux-Lock Type SFCL Using E-I Core vol.19, pp.3, 2009, https://doi.org/10.1109/TASC.2009.2017711
  13. Study on Protective Coordination for Application of Superconducting Fault Current Limiter vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2093594
  14. Quench and Recovery Characteristics of a SFCL Applied Into Neutral Line of a Three-Phase Power System vol.19, pp.3, 2009, https://doi.org/10.1109/TASC.2009.2017754
  15. Current Limiting and Recovery Characteristics of SFCLs Using Magnetic Coupling of Two Coils vol.19, pp.3, 2009, https://doi.org/10.1109/TASC.2009.2017710
  16. Method of Recloser-Fuse Coordination in a Power Distribution System With Superconducting Fault Current Limiter vol.20, pp.3, 2010, https://doi.org/10.1109/TASC.2010.2040821
  17. Study on current limiting characteristics of SFCL with two trigger current levels vol.470, pp.20, 2010, https://doi.org/10.1016/j.physc.2010.05.177
  18. Improvement of Recloser-Fuse Operations and Coordination in a Power Distribution System With SFCL vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2093595
  19. Operational Characteristics of Hybrid SFCL With First Half Cycle Non-Limiting Operation Considering Its Design Parameter vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2093597
  20. Analysis on Protection Coordination of Hybrid SFCL With Protective Devices in a Power Distribution System vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2093593
  21. Cooperation Between Reclosing System and a Flux Coupling Type SFCL by a Neutral Line vol.21, pp.3, 2011, https://doi.org/10.1109/TASC.2010.2096530