Evaluation Technique for Ratio Error of Current Transformer Comparator

전류변성기 비교기의 비오차 평가 기술

  • 김윤형 (충남대학교 전기공학과) ;
  • 한상길 (충남대학교 전기공학과) ;
  • 정재갑 (한국표준과학연구원 기반표준부 전자기그룹) ;
  • 한상옥 (충남대학교 전기공학과)
  • Published : 2008.09.01

Abstract

We have developed an evaluation technique for ratio errors of current transformer (CT) comparator by using the precise standard capacitors. By applying this technique for equivalent circuit of CT comparator evaluation system, we can obtain the calculated and measured ratio errors in the CT comparator. Thus we can evaluate ratio errors of CT comparator by comparing the calculated and measured ratio errors. Because this method requires only the standard capacitors, it is simple and easy method to reliability and accuracy maintenance of CT comparator. The method was applied to CT comparator under test with the ratio error ranges of $0{\sim}{\pm}10%$. The ratio error of the CT comparator under test theoretically obtained in this method are consistent with that measured for same CT comparator under test by using wide ratio error CT within an estimated expanded uncertainty (k = 2) in the overall ratio error ranges.

Keywords

References

  1. 한국표준협회 "계기용 변성기(표준용 및 일반 계기용)", KS C 1706, 1982
  2. 한국표준협회 "계기용 변성기-제1부:변류기", KS C IEC 60044-1, 2003
  3. Jae Kap Jung, Sung Won Kwon, Sang Hwa Lee, Jeon Hong Kang, "Calibration of Current Transformer", KRISS, C-13-2-0100-2006(E), 2006
  4. 권성원, 정재갑, 김문석, 김명수, "광범위 비오차 표준 전류변성기의 개발 및 그 응용", 대한전기학회지, 55C, 302-7, 2006
  5. 한국표준협회 "측정 결과의 불확도 추정 및 표현을 위한 지침", KS A 3000, 2005
  6. Tettex, "Automatic instrument transformer test set Type 2767", Haefely Test AG - instrument transformer measurement, 2007. (www.tettex.com)