Abstract
In this study, the ventilation system of connection passage and elevator hall of underground parking lot in apartment houses is investigated to extract the data for the installation and the application by the experimentation. In case of the elevator hall, actual air exchange rate is predicted fivefold higher than air exchange rate by infiltration and exfiltration. Ventilation system is installed good by supply air and return air. As the next best thing, it is installed by supply air because of IAQ control. The temperature of connection passage and elevator hall uniformly with $7{\sim}8^{\circ}C$, is maintained even if the operating condition of ventilation system is different. Therefore, the installation of the preheater, which is installed at the inlet of ventilation system for the cold draft in winter, is not essential in southern area of Korea.
본 논문에서는 지하주차장 연결통로 및 엘리베이터 홀의 기계식 환기장치의 설치 및 적용을 위한 기초자료를 얻기 위하여 공동주택 지하주차장에 환기장치를 설치하여 실험을 수행하였다. 엘리베이터 홀의 경우 침기 및 누기(자연환기)로 인하여 실제 환기회수는 계산환기회수의 5배 정도 크게 나타났다. 지하 주차장 연결통로 및 엘리베이터홀의 환기장치는 동시 급 배기로 설치하는 것이 좋으며, 설치가 어려울 때에는 차선책으로 급기만이라도 설치하는 것이 공기질 측면에서 좋을 것이라 판단된다. 겨울철 환기장치 가동에 따른 콜드 드래프트의 영향을 고려하여 환기장치의 급기부에 예열기를 설치하는데, 환기시스템의 가동유무 및 가동방법을 다르게 하여도 지하주차장 연결통로 및 엘리베이터 홀의 온도가 $7{\sim}8^{\circ}C$로 일정하게 유지되어 나타나므로 한국의 남부지역에서는 단순 급 배기 환기장치에 예열기를 설치하지 않아도 될 것으로 판단된다.