초록
The miniaturization of the Air Handling Unit (AHU) has become an actual need because of the restriction of the using space on the vessel. In modern AHU’s construction, in which the fan section is at the end part of the ship, it’s very difficult to select a suitable capacity of evaporators, because the fan motor emits heat. Thus, the AHU structure has been changed as the fan section has been set before the cooling coil to get temperature values similar to the designed amount. Also, the air guider is installed in order to maintain equal air distribution after it passed the fan section. So, it is possible for air to equally pass the cooling coil. It is investigated three different geometries to find the best performance. Also, It is compared with the numerical and experimental results. The study found the case 3 gives the best results. The results of this study show the possible application of the new design.