초록
In a gas insulated substation (GIS), Very Fast Transient Over-voltages (VFTOs) are generated due to switching operations and ground faults. These fast transients are associated with high frequency components of the order of a few hundreds of MHz. These transients may cause internal faults i.e., layer-to-layer faults or minor faults in a capacitively graded bushing, which is one of the important pieces of terminal equipment for GIS. In the present study, the PSPICE model has been developed to calculate the voltage distribution across the layers of 420kV graded bushing for high frequency pulses of rise time 1 to 50ns, which simulate the VFTO. For this simulation, an equivalent electrical network of bushing with different equivalent layers has been considered. The effect of different equivalent layers modeling circuits on the non-uniform voltage factor has been analysed. The influence of copper strip inductance on voltage distribution across layers has also been analysed for various rise times of high frequency transients. Finally, the leakage current of the bushing is calculated for evaluating the bushing condition under these transients.