Abstract

This paper describes the development of a novel islanding detection method, which uses the signal cross-corelation scheme between the injected reactive current and the power frequency deviation. The existing method, which injects the reactive current of 2.5-5% to the rated current and detects the frequency deviation directly, brings about lowing the power quality due to the harmonic pollution. The proposed method eliminates the weak point of the existing method, because it injects the reactive current less than 1% to the rated current. The operational feasibility was verified through computer simulations with PSCAD/EMTDC software, and experimental works with a 10kVA hardware prototype. The proposed method can detect the islanding status effectively without lowing the power quality of interconnected distributed generation system.

Keywords

References

  1. M. E. Ropp, M. Begovic, A. Rohatgi, "Determining the Relative Effectiveness of Islanding Prevention Techniques Using Phase Criteria and Non-detection Zones", IEEE Transactions on Energy Conversion Vol. 15 no. 3, September 2000, p. 290-296 https://doi.org/10.1109/60.875495
  2. IEEE Std. 929-2000, IEEE Recommended practice for Utility Interface of Photovoltaic(PV) Systems, Sponsored by IEEE Standards Coordinating Committee 32 on Photovoltaics, IEEE Std. 929-2000, Published by the IEEE, New York, NY, April 2000
  3. S. J. Ranade, N. R. Prasad, S. Omick, L. F. Kazda, "A Study of Islanding in Utility-Connected Residential Photovoltaic Systems, Part I: Models and Analytical Methods", IEEE Transactions on Energy Conversion, 4(3), pp, 436-445, September 1989 https://doi.org/10.1109/60.43246
  4. D. Handran, R. Bass, F. Lambert, J. Kennedy, "Simulation of Distribution Feeders and Charger Installation for the Georgia Tech Olympic Electric Tram System", Proceedings of the 5th IEEE Workshop on Computers in Power Electronics, pp. 168-175, August 11-14 1996
  5. Thomas R. Sims, Robert A. Jones, and Ali F. Imece, "Investigation of Potential Islanding Problems of a Line-Commutated Static Power Converter in Photovoltaic Systems." IEEE Trans. on Energy Conversion, Vol. 5, No. 3, September 1990
  6. K. Takigawa and H. Kobayashi, "A Development of Compact and Reliable Protective Control Unit for Grid Connected Small Residential PV systems." IEEE, No. CH3365-4/94/0000-1081, 1994
  7. M. A. Redfern, J. I. barrett, and O. Usta, "A New Microprocessor Based Islanding Protection Algorithm for Dispersed Storage and Generation Units." IEEE Trans. on Power Delivery, Vol. 10, No. 3, July 1995
  8. P. O'Kane and B. Fox, "Loss of mains Detection for Embedded Generation by System Impedance Monitoring." IEE Conference Publication on Developments in Power System Protection, 25-27th March 1997
  9. Cooper C B, "Standby Generation Problems and Prospective Gains from Parallel Running." Power System Protection '89, Singapore 1989
  10. Ropp, ME., Begovic, M., and Rogatgi, A. : "Analysis and performance assessment of the active frequency drift method of islanding prevention", IEEE Trans. Energy Convers., 1999, 14, (3), pp. 810-816 https://doi.org/10.1109/60.790956
  11. Hung, G.K., Chang, C.C., and Chem, C.L. :" Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters", IEEE Trans, Energy Convers., 2003, 18, (1), pp. 169-173 https://doi.org/10.1109/TEC.2002.808412
  12. B. Han, B. Bae, "Novel Phase-Locked Loop Using Adaptive Linear Combiner" IEEE Trans on Power Dilivery, Vol. 21, No. 1, Jan, 2006