EMTP-MODELS를 이용한 Multi-Agent System 기반의 자동 재폐로 계전 알고리즘 구현

Implementation of Auto-reclosing Relay Algorithm based on Multi-Agent System using EMTP-MODELS

  • 이병현 (성균관대학교 정보통신공학부) ;
  • 여상민 (성균관대학교 정보통신공학부) ;
  • 이유진 (성균관대학교 정보통신공학부) ;
  • 김철환 (성균관대학교 정보통신공학부) ;
  • 성노규 (성균관대학교 정보통신공학부)
  • 발행 : 2008.01.01

초록

This paper presents auto-reclosing algorithms with reference to power system stability based on MAS(Multi-Agent System). And this paper shows auto-reclosing algorithms considering power system stability. It includes the variable dead time, optimal reclosing, sequential reclosing, emergency extended equal-area criterion(EEEAC) algorithm, and modified EEEAC algorithm. This paper divides Auto-reclosing algorithms into respectively agents according to their tasks. A separated agent is merely a software entity that is situated in some environment and is able to autonomously react to changes in the environment. And all the simulations in this parer were tested by EMTP MODELS.

키워드

참고문헌

  1. S.P. Ahn, C.H. Kim, R.K. Aggarwal, A.T. Johns, "An Alternative Approach to Adaptive Single Pole Auto-Reclosing in High Voltage Transmission Systems Based on Variable Dead Time Control", IEEE Trans. on Power Delivery, Vol. 16, No. 4. pp. 667-677, 2001 https://doi.org/10.1109/63.949499
  2. 허정용, "전력계통의 안정도를 고려한 자동 재폐로 알 고리즘에 관한 연구", 성균관대학교 석사학위 졸업논문, 2003
  3. A.M. El-Serafi, S.O. Faried, "Effect of Sequential Reclosure of Multi-phase System Faults on Turbine-Generator Shaft Torsional Torques", IEEE Trans. on Power Systems, Vol. 6, No. 4, pp. 1380-1388, Nov. 1991 https://doi.org/10.1109/59.116979
  4. Hui Wan, K. K. Li, K. P. Wong, "An Multi-Agent Approach to Protection Relay Coordination with Distributed Generators in Industrial Power Distributed System", IEEE Digital Object Identifier, pp. 830-836, Oct. 2005
  5. 소광훈, "과도안정도를 고려한 동기탈조 검출 알고리즘 에 관한 연구", 석사학위 졸업논문, 성균관대학교, 2003
  6. S. Goldberg, W.F. Horton, D. Tziouvaras, "A Computer Model of the Secondary Arc in Single Phase Operation of Transmission Lines", IEEE Trans. on Power Delivery, Vol. 4, No. 1, pp. 586-594, Jan. 1989 https://doi.org/10.1109/59.193833