절연전선 결함 위치 추정에 대한 시간-주파수 영역 반사파 계측법의 적용

Estimation of Fault Location on a Power Line using the Time-Frequency Domain Reflectometry

  • 두승호 (연세대학교 전기전자공학과) ;
  • 곽기석 (연세대학교 전기전자공학과) ;
  • 박진배 (연세대학교 전기전자공학과)
  • 발행 : 2008.02.01

초록

In this paper, we introduce a new method for detecting and estimating faults on a power line using the time-frequency domain reflectometry system. The system rests upon time-frequency signal analysis and uses a chirp signal which is multiplied by Gaussian envelope. The chirp signal is used as a reference signal, and we can get the reflected signal from a fault on a wire. To detect and estimate faults, we analyze the reflected signal by Wigner time-frequency distribution function and normalized time-frequency cross correlation function. In this paper we design an optimal reference signal for power line and implement a system for estimating fault distance on a power line with the TFDR implemented by PXI equipments. This approach is verified by some experiments with HIV 2.25mm power lines.

키워드

참고문헌

  1. 전기안전공사, "전기 재해 통계 보고서,' 2005
  2. Hewlett Packard, "Time Domain Reflectometry,' Hewlett Packard, 1998
  3. Van Hamme, H., "High-resolution frequency-domain reflectometry by esitmation of modulated superimposed complex sinusoids,' IEEE Transactions on Instrumentation and Measurement, Volume: 41, Issue: 6, Pages: 762-767, Dec. 1992 https://doi.org/10.1109/19.199407
  4. Site Master, "Transmission Line and Antenna Analyzer : Datasheet,' Anritsu, Aprill 2000
  5. Yamada, H., Ohmiya, M., Ogawa, Y. and Itoh, K., "Superresolution techniques for time-domain measurements with a network analyzer", Antennas and IEEE Transactions on Propagation, Vol. 39, pp. 177-183, Feb. 1991 https://doi.org/10.1109/8.68179
  6. Agrez, D., "Approximation of the skin effect to improve cable-fault location by TDR," Instrumentation and Measurement Technology Conference 2003, Proceedings of the 20th IEEE, Vol. 1, pp. 50-53, May 20-22, 2003
  7. Stoica, P., Taniguchi, T., Ohska, T.K., Kurashige, H., "A high resolution TDC in TKO box system,' IEEE Transactions on Nuclear Science, Volume: 35, Issue: 1, Pages: 342-347, Feb. 1988 https://doi.org/10.1109/23.12739
  8. Yong-June Shin et al., "Application of Time-Frequency Domain Reflectometry for Detection and Localization of a Fault on a Coaxial Cable,' IEEE Transactions on Instrumentation and Measurement, Volume: 54, Number: 6, Pages: 2493-2500, Dec. 2005 https://doi.org/10.1109/TIM.2005.858115
  9. 최덕선, 곽기석, 윤태성, 박진배, "시간-주파수 반사파 계측 방법을 이용한 전송선로의 결함 위치 추정," 대한전기학회논문지, 제54권 9호, pp. 521-530, 2005