A Study on the Standard for Installation of Carbon Monoxide Detector in a Building

건축물내 일산화탄소 경보기 설치기준에 관한 연구

  • 강승규 (한국가스안전공사 가스안전연구원) ;
  • 최경석 (한국가스안전공사 가스안전연구원)
  • Published : 2008.12.30

Abstract

In the last five years, 36 people died and 79 were wounded because of carbon monoxide poisoning accident. A CO poisoning accident is higher than any other gas accident in the rate of deaths/incidents. Most of these CO poisoning accidents were caused by defective exhaust tube in the old gas boiler and multi-use facility. In this study, the spread mechanism of CO gas released from leakage hole of exhaust tube was analyzed by concentration measuring test. A CO gas leaked form exhaust tube in a building was the highest concentrated near the ceiling. CO alarm sets installation test confirmed that the alarm sets near the ceiling operated first, and the bottom and middle sets operated after $30{\sim}40$ minutes. Through these experiments, the reasonable installation location of CO alarm was made certain and suggested.

최근 5년간 국내 가스사고 중 CO중독사고는 사망 36명, 부상 79명이 발생하였으며, 전체 가스 사고에 비해 인명피해율이 8배나 높게 나타나고 있다. 이러한 CO중독사고의 대부분이 노후 가스보일러 및 다중 가스 사용시설의 배기통 불량에 의한 가스누출사고로 조사되고 있다. 본 연구에서는 실험을 통해 건축물 내 보일러실의 배기통 불량에 의한 CO가스의 누출확산 메커니즘을 해석하였다. 배기통에서 누출된 CO 가스는 건축물 내부의 천정부근에서 가장 높은 농도분포를 보인다. 또한 CO경보기 설치 실험을 통해서 천정부근의 CO경보기가 가장먼저 작동하고, $30{\sim}40$분 경과한 후에 바닥 및 중간에 설치된 경보기가 작동하는 것을 확인하였다. 본 연구를 통해 CO경보기의 적정 설치위치를 확인하였으며, 이 결과를 토대로 건출물내 CO경보기 설치위치를 제안하였다.