DOI QR코드

DOI QR Code

Ungrounded System Fault Section Detection Method by Comparison of Phase Angle of Zero-Sequence Current

  • Yang, Xia (Dept. of Electrical Engineering, Myongji University) ;
  • Choi, Myeon-Song (Dept. of Electrical Engineering, Myongji University) ;
  • Lee, Seung-Jae (Dept. of Electrical Engineering, Myongji University) ;
  • Lim, Il-Hyung (Dept. of Electrical Engineering, Myongji University) ;
  • Lim, Seong-Il (Dept. of Electrical and Electronic Engineering, KyungNam University)
  • Published : 2008.12.01

Abstract

In this paper, an integrated fault section detection and isolation strategy is proposed based on the application of the Distribution Automation System(DAS) utilizing advanced IT and communication technologies. The Feeder Remote Terminal Unit(FRTU) has been widely used to collect data in the Korean distribution system. The achieved data is adopted in this method for detecting multiple fault types. Especially in the case of single phase-to-ground fault, the fault section is detected by comparison of the zero-sequence current phase angle. The test results have verified the effectiveness of the proposed method in a radial distribution system through extensive simulations in Matlab/Simulink. Furthermore, a communication-based demo system identical to the simulation model has been developed, and it can be applied as an online monitoring and control program for fault section detection and isolation.

Keywords

References

  1. Raymond O. D. Whitt, 'Trends and practices in grounding and ground fault protection using static devices', IEEE Transactions on Industry Applications, Vol. IA-9, Issue 2, March, 1973
  2. Bingyin Xu, Yongduan Xue, Jing Li, Yu Chen, 'Single phase fault detection technique based on transient current and its application in non-solid grounded network', IEE conference in Developments in Power System Protection, No. 479, 2001
  3. Pan Zhengcun, Zhang Huifen, Zhang Fan and Sang Zaizhong, 'Analysis and Modification of Signal Injection Based Fault Line Selection Protection', Automation of Electric Power Systems, Vol. 31 No. 4, Feb. 25, 2007
  4. Xia Yang, Seong-Il Lim, Seung-Jae Lee, Myeon-Song Choi, 'Communication-based Fault Handling Scheme for Ungrounded Distribution System', Energy and Power Systems (EPS2006), March, 2006
  5. Qiang Guan, Myeon-Song Choi and Seung-Soo Han, 'IEC61850 Based FRTU Development Scheme', KIEE summer conference, July 2007
  6. J. Lewis Blackburn, Thomas J. Domin, Protective Relaying: Principles and Applications, Third Edition (Power Engineering), pp. 191-195, CRC, 2006
  7. Hong-chun Shu, Bai Xiao, 'A novel fault line selection algorithm of single-phase ground faults in ungrounded neutral system using wavelets transform', PowerCon 2002, Vol. 4, pp. 2532-2536, Oct. 2002
  8. Qianli Su, Xinzhou Dong, Shenxing Shi, Bin Su, Jiali He, 'A new principle of fault line selection for distribution', IEE Seventh International Conference on Developments in Power System Protection, pp. 379-382, April 2001
  9. Zheng Qi, Yihan Yang, 'Study on line selection in non-effectively grounded system based on wavelet transform and Wiener filter', IEEE Power Engineering Society General Meeting, Vol.1, pp. 89-93, June 2004
  10. Chengyong Zhao, Yanfen Guo, Gengyin Li, 'The similitude power detection on singlephase-to-ground fault in the non-solidly grounded system', IEEE/PES Transmission and Distribution Conference & Exhibition: Asia and Pacific Dalian, China, 2005
  11. J. C. Das, Power System Analysis - Short-Circuit Load Flow and Harmonics, pp. 42-43, Marcel Dekker, Inc. 2002