DOI QR코드

DOI QR Code

Two-Terminal Numerical Algorithm for Single-Phase Arcing Fault Detection and Fault Location Estimation Based on the Spectral Information

  • Published : 2008.12.01

Abstract

This paper presents a new numerical algorithm for the fault location estimation and arcing fault detection when a single-phase arcing ground fault occurs on a transmission line. The proposed algorithm derived in the spectrum domain is based on the synchronized voltage and current samples measured from the PMUs(Phasor Measurement Units) installed at both ends of the transmission lines. In this paper, the algorithm uses DFT(Discrete Fourier Transform) for estimation. The algorithm uses a short data window for real-time transmission line protection. Also, from the calculated arc voltage amplitude, a decision can be made whether the fault is permanent or transient. The proposed algorithm is tested through computer simulation to show its effectiveness.

Keywords

References

  1. T. Takagi, et al., 'Development of a new fault locator using the one-terminal voltage and current data,' IEEE Trans. on PAS, vol. PAS-101, No. 8, pp. 2892-2898, August 1982 https://doi.org/10.1109/TPAS.1982.317615
  2. L. Eriksson, M. Saha, and G.D. Rockfeller, 'An accurate fault locator with compensation for apparent reactance in the fault resistance resulting from remote-end in feed,' IEEE Trans. on PAS, Vol. PAS-104, No. 2, pp. 424-436, Feb. 1985
  3. M. Sant and Y. Paithankar, 'One line digital fault locater for overhead transmission line,' IEE Proceedings, Vol. 126, No. 11, pp. 1181-1185, Nov. 1979
  4. Y.-H. Lin, C.-W. Liu, and C.-S. Chen, 'A new PMU-based fault detection/location technique for transmission line with consideration of arcing fault discrimination-Part 1: theory and algorithm,' IEEE Trans. on Power Del., vol. 19, No. 4, pp. 1587-1593, Oct. 2004 https://doi.org/10.1109/TPWRD.2004.832407
  5. Y.-H. Lin, C.-W. Liu, and C.-S. Chen, 'A new PMU-based fault detection/location technique for transmission line with consideration of arcing fault discrimination-Part 2: performance evaluation,' IEEE Trans. on Power Del., Vol. 19, No. 4, pp. 1594-1601, Oct. 2004
  6. J. G. McNeff, 'The global positioning system,' Microwave theory and Techniques, IEEE Transaction on. vol. 50, No. 3, pp. 645-652, March 2002 https://doi.org/10.1109/22.989949
  7. Z. Radojevic, V. Terzija, M. Duric, 'Numerical Algorithm for Overhead Lines Arcing Faults Detection and Distance and Directional Protection,' IEEE Transactions on Power Delivery, Vol. 15, No. 1, January 2000, pp. 31-37 https://doi.org/10.1109/61.847225
  8. M.Djuric, V.Terzija, 'A new approach to the arcing faults detection for autoreclosure in transmission systems,' IEEE Trans. on Power Delivery, Vol. 10, No. 4, Oct. 1995, pp. 1793-1798 https://doi.org/10.1109/61.473378

Cited by

  1. Fault pattern recognition of gas blower based on discrete Fourier transform interpolation algorithm vol.9, pp.3, 2017, https://doi.org/10.1177/1687814017694819