A Numerical Algorithm for Fault Location Estimation Considering Long-Transmission Line

장거리 송전선로를 고려한 사고거리추정 수치해석 알고리즘

  • Published : 2008.12.01

Abstract

This paper presents a numerical algorithm for fault location estimation which used to data from both end of the transmission line. The proposed algorithm is also based on the synchronized voltage and current phasor measured from the PMUs(Phasor Measurement Units) in the time-domain. This paper has separated from two part of with/without shunt capacitance(short/long distance). Most fault was arc one-ground fault which is 75% over [1]. so most study focused with it. In this paper, the numerical algorithm has calculated to distance for ground fault and line-line fault. In this paper, the algorithm is given with/without shunt capacitance using II parameter line model, simple impedance model and estimated using DFT(Discrete Fourier Transform) and the LES(Least Error Squares Method). To verify the validity of the proposed algorithm, the EMTP(Electro- Magnetic Transient Program) and MATLAB did used.

Keywords

References

  1. M. B. Djuric, V.V. Terzija, " A New Approach to the Arcing Faults Detection for Autoreclosure in Transmission Systems", IEEE Trans. on Power Delivery, Vol. 10, No.4, pp. 1793-1798, 1995 https://doi.org/10.1109/61.473378
  2. M. B. Djuric, Z.M. Radojevic, V.V. Terziia, "Arcing Faults Detection on Transmission Lines using Least square Technique", ETEP, Vol. 8, No.6, pp. 437-443, Nov/Dec 1998 https://doi.org/10.1002/etep.4450080605
  3. Z.M. Radojevic, C.J. Lee, J,R. Shin, J.B. Park, "Numerical Algorithm for Fault Distance Calculation and Blocking Unsuccessful Reclosing onto Permanent Faults", IEEE PES Gen., June 2005
  4. M.B. Djuric, Z.M. Radojeic, V.V. Terzija, "Numerical Algorithm for Arcing Faults Detection and Fault Distance Calculation on overhead line", Electric Machines and Power System, pp. 939-953. 1977.
  5. Zoran Radojevic, Joong-Rin Shin, "A New one-Terminal Numerical Algorithm for Adaptive Autoreclosure and Fault Distance Calculation", Tran KIEE, Vol.53A, No.8, Aug. 2004, pp438-445
  6. H. Lee, A.M. Mousa,"Gps Traveling Wave Fault Locator System: Investigation into the Anomalous Measurements Related to lighting Strikes", IEEE Trans Power Delivery, Vol. 11, pp.1214-1223, Jul.1996 https://doi.org/10.1109/61.517474
  7. A.H. Osman, O.P.Malik,"Protection of Parallel Transmission Lines using Wavelet Transform", IEEE Trans Power Delivery, Vol. 11, No.1, pp.49-55, Jan. 2004
  8. Ying-Hong Lin, Chih-Wen Liu, Ching-Shan Chen, "A New PMU-Based Fault Dectection/Location Techique for Tranmission Line with Consideration of Arcing Fault Discrimination-Part I :Theory and Algorithms", IEEE Trans. on Power Delivery, Vol. 19, No.4, pp. 1587-1593, Oct. 2004. https://doi.org/10.1109/TPWRD.2004.832407
  9. Ying-Hong Lin, Chili-Wen Liu, Ching-Shan Chen, "A New PMU-Based Fault Dectection/Location Techique for Tranmission Line with Consideration of Arcing Fault Discrimination-Part II :Performance Evaluation", IEEE Trans. on Power Delivery, Vol. 19, No.4, pp.1594-1601, Oct. 2004 https://doi.org/10.1109/TPWRD.2004.835276
  10. A. Maikapar, "Extinction of an Open Electric Arc", Elektrichestvo, Vol. 4, pp. 64-69, 1960
  11. A.T. Johns, RK. Aggarwal, Y.H. Song, "Improved Techniques for Modeling Fault Arcs on Faulted EHV Transmission Systems", IEE Proc. Gener. Transm. Distrib., Vol. 141, No.2, pp. 148-154, March 1994 https://doi.org/10.1049/ip-gtd:19949869
  12. M. Kezunovic, B. Pernunicic, "Automatic Transmission Line Fault Analysis using Synchronized Sampling at Two End", IEEE Trans on Power System, Vol 11, No.1, pp 441-447, Feb 1996 https://doi.org/10.1109/59.486131