Frost Behavior on a One-Dimensional Fin Considering Heat Conduction of Heat Exchanger Fins

열교환기 휜의 열전도를 고려한 1차원 휜에서의 착상 거동

  • Kim, Jung-Soo (School of Mechanical Engineering, Hanyang University) ;
  • Kang, Soo-Jin (School of Mechanical Engineering, Hanyang University) ;
  • Lee, Kwan-Soo (School of Mechanical Engineering, Hanyang University)
  • 김정수 (한양대학교 대학원 기계공학과) ;
  • 강수진 (한양대학교 대학원 기계공학과) ;
  • 이관수 (한양대학교 기계공학과)
  • Published : 2008.11.10

Abstract

This paper presents a mathematical model to predict the behavior of frost formed on an one-dimensional fin of heat exchanger, considering fin heat conduction under frosting conditions. The computational domain consists of air-side, the frost layer, and fin region, and they are coupled to the frost layer. The frost behavior is more accurately predicted with fin heat conduction considered (Case A) than with constant fin surface temperature assumed (Case B). The results indicate that for Case B, the frost thickness and heat transfer are overpredicted in most regions of the fin, as compared with those for Case A. In addition, for Case A, the maximum frost thickness varies little with the fin length variations, and the extension of the fin length after 30mm contributes insignificantly to heat transfer.

Keywords

References

  1. Seker, D., Karatas, H. and Egrican, N., 2004, Frost formation on fin-and-tube heat exchangers, Part I-Modeling of frost formation on fin-and-tube heat exchangers, Int. J. Refrigeration, Vol. 27, pp. 367-374 https://doi.org/10.1016/j.ijrefrig.2003.12.003
  2. Kondepudi, S. N. and O'Neal, D. L., 1993, Performance of finned-tube heat exchangers under frosting conditions. I. Simulation model, Int. J. Refrigeration, Vol. 16, No. 3, pp. 175-180 https://doi.org/10.1016/0140-7007(93)90045-A
  3. Yang, D. K., Lee, K. S. and Song, S., 2006, Modeling for predicting frosting behavior of a fin-tube heat exchanger, Int. J. Heat and Mass Transfer, Vol. 49, pp. 1472-1479 https://doi.org/10.1016/j.ijheatmasstransfer.2005.09.022
  4. Chen, H., Thomas, L. and Besant, R. W., 2003, Fan supplied heat exchanger fin performance under frosting conditions, Int. J. Refrigeration, Vol. 26, pp. 140-149 https://doi.org/10.1016/S0140-7007(02)00011-7
  5. Tso, C. P., Cheng, Y. C. and Lai, A. C. K., 2006, An improved model for predicting performance of finned tube heat exchanger under frosting condition, with frost thickness variation along fin, Applied Thermal Engineering, Vol. 26, pp. 111-120 https://doi.org/10.1016/j.applthermaleng.2005.04.009
  6. Kaygusuz, K., 1994, Performance of an air-to-air heat pump under frosting and defrosting conditions, Applied Energy, Vol. 48, pp. 225-241 https://doi.org/10.1016/0306-2619(94)90012-4
  7. Miller, W. A., 1983, Frosting Experiments for a heat pump having a one-row spine-fin outdoor coil, ASHRAE Journal-American Society of Heating Refrigerating and Air-Conditioning Engineers, Vol. 25, No. 12, pp. 74-74
  8. Wang, S. W. and Liu, Z. Y., 2005, A new method for preventing HP from frosting, Renewable Energy, Vol. 30, pp. 753-761 https://doi.org/10.1016/j.renene.2003.07.001
  9. Martinez-Frias, J. and Aceves, S. M., 1998, Modeling of a heat pump with evaporator air dehumidification for reduced frost formation, Heat pump and refrigeration systems, design, analysis, and application, pp. 305-312
  10. Sami, S. M. and Duong, T., 1989, Mass and heat transfer during frost growth, ASHRAE Transactions, Vol. 95, pp. 158-165
  11. Ismail, K. A. R. and Salinas, C. S., 1999, Modeling of frost formation over parallel cold plates, Int. J. Refrigeration, Vol. 22, No. 5 pp. 425-441 https://doi.org/10.1016/S0140-7007(98)00069-3
  12. Lee, K. S., Kim, W. S. and Lee, T. H., 1997, A one dimensional model for frost formation on a cold flat surface, Int. J. Heat and Mass Transfer, Vol. 40, No. 18, pp. 4359-4365 https://doi.org/10.1016/S0017-9310(97)00074-4
  13. Lee, K. S., Jhee, S. and Yang, D. K., 2003, Prediction of the frost formation on a cold flat surface, Int. J. Heat and Mass Transfer, Vol. 46, pp. 3789-3796 https://doi.org/10.1016/S0017-9310(03)00195-9
  14. Kwon, J. T., Lim, H. J., Kwon, Y. C., Koyama, S., Kim, D. H. and Kondou, C., 2006, An experimental study on frosting of laminar air flow on a cold surface with local cooling, Int. J. Refrigeration, Vol. 29, pp. 754-760 https://doi.org/10.1016/j.ijrefrig.2005.12.009
  15. ASHRAE HANDBOOK, 1993, Fundamentals. ASHRAE Atlanta