Abstract

This paper summarize about the auxiliary electrode measured a ground resistance. The method to measure a ground resistance is the fall-of-potential method to using an auxiliary electrode. And an auxiliary electrode must be set up on the ground. Today it is so difficult to set up the auxiliary electrode on the ground because of many concrete building and many paved roads. So this paper is regarding a trust analysis of the ground resistance measurement by the substitute auxiliary electrode. It substituted a iron structure around the building, a neutral line multiplex ground to earth, a wire net for auxiliary electrode. This information is confirmed bv compared with the measurement value.

Keywords

References

  1. 산업자원부, '전기설비기술기준', pp. 14-20
  2. 高僑倦彦, '접지기술입문', 동일출판사, pp. 203-225 2002
  3. 이복희, 엄주홍, '전위강하법에 의한 접지저항측정에 미치는 전류보조전극의 영향', 조명전기설비학회 논문지, 6호, 제14권, pp. 69-77, 2000. 1
  4. Kenneth M. Michaels, 'Earth Ground Resistance Testing for Low-Voltage Power Systems', IEEE Transactions on Industry Applications, Vol. 31, No. 1, pp. 206-213, 1995 https://doi.org/10.1109/28.363027
  5. KSC 1310, '접지저항계', 1999
  6. 대한전기협회 '내선규정', pp. 541, 2004
  7. Power System Instrumentation and Measurements Committee, 'IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System', IEEE Std 81-1983, pp. 17-24