DOI QR코드

DOI QR Code

An Analysis of the Relationship between Elevator Emergency(Entrapment) and Situation Measurement of Sag/Interruptions at the Switchboard

  • Kim, Gi-Hyun (Electrical Safety Research Institute) ;
  • Lim, Young-Bae (Korea Electrical Safety Corporation at the Electrical Safety Research Institute) ;
  • Bai, Seok-Myung (Korea Electrical Safety Corporation at the Electrical Safety Research Institute) ;
  • Kim, Jae-Chul (Department of Electrical Engineering Soongsil Univ.) ;
  • Lee, Hee-Tae (Electrical Engineering Soongsil Univ.)
  • Published : 2007.05.31

Abstract

This study researched the mutual relationship between elevator emergencies(sudden stops, entrapment) and power quality such as voltage interruptions or sags. To analyze the power quality at the elevator switchboard of an apartment, the on-line power quality(sag, swell, and interruption, etc.) were measured and error messages(under voltage error, etc.) in the elevator control room were researched. Also the performance and susceptibility for stops were evaluated and stated through the testing of three pieces of simulated test equipment with an EN12016(2004) standard setting and the magnitude and duration data of the measured sag or interruption. This paper will use these data in the analysis of the mutual relationship between power quality and elevator emergencies.

Keywords

References

  1. Statistics data of Korea Elevator Safety Institute (Web site : www. Kesi.or.kr, 2006)
  2. KEPCO, 'Paper of Distribution Fault analysis and protection', 2005 Distribution Part
  3. Gi-Hyun, Kim et 3, The cause analysis and research of malfunction for elevator equipment of the apartment house , Journal of KIIEE, Vol 20, No.4, pp. 65-71, May 2006 https://doi.org/10.5207/JIEIE.2006.20.4.065
  4. Gi-Hyun, Kim et 2, The Study of measurement and performance evaluation for elevator equipment by Instantaneous power quality, journal of KIIEE, Vol 20, No. 5, pp. 42-48, June 2006 https://doi.org/10.5207/JIEIE.2006.20.5.042
  5. Sag Project Plan Basics for customer. WESCOV, 2006 paper
  6. Gi-Hyun, Kim et 3,, Relation between event of keptwithin elevator and sag generation at APT by lighting , KIIEE Autumn Annual Conference 2006, pp 245-250, 2006. 11
  7. EN 12016(Electromagnetic Compatability : Product family standard for lifts, escalators and moving walks-Immunity)
  8. Electromagnetic compatibility(EMC) -Part 4 : Testing and measurement techniques - Section 11 : Voltage dips, short interruptions and voltage variations immunity tests(2004)
  9. Recommended practice for monitoring electric power Quality R(1995)
  10. Are Voltage Sages destroying Equipment ? : IEEE Industry Applications magazine 2006. 7