A Study on the Electric Shock due to Submerged Power Source

침수 상용전원에 의한 감전위험성 검토

  • 정종욱 (한국전기안전공사 전기안전연구원) ;
  • 정진수 (한국전기안전공사 전기안전연구원 설비안전연구그룹)
  • Published : 2007.07.31

Abstract

This paper describes a risk assessment of electric shock based on a experiment which demonstrates a submerged commercial power source. For the experiment a water tank was made and an outlet was installed on an interior wall. After filling the tank with a conductive water solution, the electric potential was measured with the distance, the direction from the power source, the conductivity and the level of the water solution. As a result, the potential distribution due to the outlet energized and exposed to the water solution depends on the distance from the submerged power source, however, the direction from the power source, the conductivity and the level of the water solution seemed to scarcely affected on the electrical shock risk.

본 논문에서는 상용전원이 침수되었을 경우, 이에 의한 인체 감전의 위험성을 실증실험을 통해 검토하였다. 실험을 위해 한쪽 벽면에 노출된 충전부가 설치된 모의수조를 구축하고 내부에 도전성 수용액을 채운 후, 전원으로부터의 거리, 방향, 도전성 수용액의 전도율 및 수위에 따른 전위를 측정하였다. 실험 결과 수중에 설치된 전원장치로 인한 전위분포는 거리에 따라 달라지지만, 침수 수용액의 도전율, 노출된 충전부로부터의 각도 및 측정높이는 전기적으로 미치는 영향이 거의 없음이 확인되었다.

Keywords

References

  1. 윤용남, 지하공간의 침수방지대책에 관한 연구, 행정자치부, pp. 5-69, 2004
  2. 김두현, 강동규, 이종호, '지상과 수중에서 전격에 의한 위험성 평가', 산업안전학회지, 제19권, 제2호, pp. 26-33, 2004
  3. IEC Publication 60479-1 : 'Effects of current on human beings and livestock', 2005
  4. 타카하시 타케히코, 접지.등전위 본딩설계의 실무지식, 성안당, pp. 31-32, 2004