Abstract
In this paper, a simulation method of the internal winding fault is proposed to calculate winding current and electromagnetic force in a distribution power transformer by suing FEM program. The model of the transformer is a single phase, 60[Hz], 1[MVA], 22.9[kV]/220[V], cable-type winding. The short-circuit current and electromagnetic force are calculated by FEM(Finite Element Method) program(Flux2D) and the results we verified with theoretical formula and PSPICE program. The simulation results are fairly good agreement with the other verified methods within 5[%] error rate. The turn-to-turn short-circuit current is 500 times of the rated current and the electromagnetic force is about $20{\sim}200times$. The method presented in this study may serve as one of the useful tools in the electromagnetic force analysis of the transformer winding behavior under the short circuit condition for design of the structure.
본 논문에서는 전력계통에서 발생되는 surge나 고장전류에 의해서 변압기의 고압측 권선에 선간단락이 발생할 경우 유도되는 전자력의 크기를 유한요소 전자계해석 프로그램을 이용하여 해석하는 방법을 제안하였다. 연구에서 사용된 배전용 변압기 model은 1[MVA], 22,900/220[V] 단상 외철형 Cable 권선형 변압기로서 권선간 단락을 모의하는 방법을 제안하고, FEM 프로그램(FLUX2D)을 이용하여 단락전류와 각방향의 전자력을 계산하고 분석하였다. 누설자속분포, 권선단락 시 전압 및 전류파형, 권선간에 작용하는 힘의 변화와 분포를 계산하였다. Simulation 방법의 타당성을 검증하기 위하여 이론치와 Pspice 프로그램을 이용하여 계산한 결과와 5[%] 이내의 오차율로 아주 잘 일치함을 확인하였다. 선간단락전류는 정격전류의 약 400배이며, 전자력도 $20{\sim}200$배 정도로 급증하였다. 본 연구의 결과는 배전용 변압기의 신뢰도 향상을 위하여 변압기 코일과 절연구조 설계에 유용한 정보를 제공하게 될 것이다.