DOI QR코드

DOI QR Code

A Study on Harmonics Analysis and Modelling for Distribution System

배전 시스템의 고조파 분석 및 모델링에 관한 연구

  • 왕용필 (동아대학교 전기공학과) ;
  • 정종원 (동아대학교 전기공학과) ;
  • 정동일 (부산동의공업고등학교 전기과)
  • Published : 2007.03.31

Abstract

The increasing use of power electronic equipment in distribution system has been the reason for the greater concern about a harmonic in recent time. Therefore, it is necessary for measurement and modelling to analyze a harmonic level and a transfer characteristic in distribution system. In this paper, the Point of Common Coupling (PCC) is selected to analyze harmonic characteristic of distribution system by IEC 61000-3-6. Harmonic voltage and orient were measured at the PCC of real distribution system Harmonic distribution, nonlinear load component and Total Harmonic Distortion(THD) were verified. The effective and accurate modelling of real distribution system were proved through a analysis of harmonic impedance, voltage and current under steady-state. Harmonic transfer characteristic were investigated through a analysis of harmonic voltage and current under harmonic current source.

최근 전력 전자 응용 기기의 사용증가로 비선형 특성 부하에 의한 고조파가 상당히 발생하고 있으며, 이에 의한 영향으로 배전시스템의 변압기 열화, 소자의 고장, 통신 간섭 등의 여러 가지 문제를 발생시키고 있다. 따라서 배전 시스템에서의 고조파 수준과 전달특성을 정확하게 분석하기 위하여 배전시스템의 효과적인 실측정과 모델링에 관한 연구가 필요한 실정이다. 본 논문에서는 고조파 관리기준 IEC61000-3-6 토대로 배전 시스템의 고조파 특성을 해석하기 위하여 공통 결합점(Point of Common Coupling : PCC)을 선택하였다. 실 배전 시스템의 PCC 지점에서 고조파 전압, 전류를 측정하여, 고조파 분포, 비선형 부하 성분 및 고조파 전압, 전류 왜형률 (Voltage/Current Total Harmonic Distortion: VTHD/ITHD)을 분석하였다. 또한 정상상태에서 고조파 임피던스, 전압, 전류을 해석을 통하여 실 배전시스템을 효과적이고 정확하게 모델링 되었을 확인하였다. 또한 고조파 전류원 발생시에 고조파 전압, 전류를 비교 분석하여 고조파 전달특성을 조사하였다.

Keywords

References

  1. Stones. J and Cillinson. A, 'Power quality', Power Engineering Journal, Vol. 15, 2, pp.58 - 64, April 2001 https://doi.org/10.1049/pe:20010201
  2. Mack Grady. W and Santoso, S, 'Understanding power system harmonics', Power Engineering Review, IEEE, Vol. 21, pp.8-11, Nov. 2001
  3. IEC 1000-3-6, 'Electromagnetic CompatibiIity, PART3 : Section6 : Assessment of emission limits for distorting loads in MV and HV power systems.', 1996
  4. Zhou Yong, 'Harmonic sources in the city distribution system', Advances in Power System Control, Operation and Management, 1997. APSCOM-97. Fourth International Conference, Volume: 2 , pp:549 - 551, Nov. 1997
  5. McGranaghan, M., 'Overview of the guide for applying harmonic limits on power systems-IEEE P519A', Harmonics And Quality of Power, 1998. Proceedings. 8th International Conference, Vol. 1, pp.462 - 469, Oct. 1998
  6. 'PSCAD/EMTDC Power System Simulation Software Manual', Monitoba HVDC Research Centre, 1996