Abstract
This paper presents the effects of the injected number and amplitude of impulse current on the service life of ZnO varistors for low voltages. To analyze the effects of lightning impulse currents on the performance of ZnO varistors, the measurements of resistive leakage current and power dissipation at the power frequency ac voltage before and after the injections of the $8/20[{\mu}s]$ impulse currents were made. As a consequence, the duration and amplitude of resistive leakage current flowing through ZnO varistor were increased with increasing the number of injections of the $8/20[{\mu}s]$ impulse currents. It is desirable that the service life of ZnO varistors should be evaluated as a function of the number and amplitude of lightning impulse current.
본 논문에서는 임펄스전류의 크기와 인가횟수가 ZnO바리스터의 수명에 미치는 영향에 관한 것으로 뇌임펄스전류가 ZnO바리스터의 성능에 미치는 영향을 분석하기 위하여 $8/20[{\mu}s]$임펄스전류가 인가되기 전후 ZnO바리스터의 상용주파수 교류전압에 대한 저항성 누설전류와 손실전력을 측정하였다. 그 결과 $8/20[{\mu}s]$임펄스전류의 인가횟수가 증가함에 파라 ZnO바리스터에 흐르는 저항성 누설전류는 증가하고 통과시간은 길어졌다. ZnO바리스터의 수명은 뇌임펄스전류의 크기와 인가횟수에 대해서 평가하는 것이 바람직하다.