DOI QR코드

DOI QR Code

Temperature Rise and Dielectric Characteristics of Distribution Transformers with Over-Loading Operation

배전용변압기의 부하운전에 의한 온도 및 유전특성 분석

  • 김병숙 (한전전력연구원 배전연구소) ;
  • 이병성 (배전연구소 배전설비그룹) ;
  • 송일근 (전력연구원 배전연구소 배전설비그룹) ;
  • 한병성 (전북대학교 전자정보공학부) ;
  • 정종만 (한전전력연구원 배전연구소)
  • Published : 2007.01.31

Abstract

Temperature rise characteristics of medium voltage class transformers and dielectric characteristics of its insulation oil according to the loading rate were investigated using the transformer that has thermocouples embedded in the windings. The hottest-spot of the transformer locates at about 2/3 height of the windings where they adjoin each other among the 3 phase windings. The temperature difference between the hottest-spot and top-oil is about $17[^{\circ}C]$ and the value keeps uniformly in short time after changing the loading rate. Capacitance of the oil varies in inverse proportion to temperature and the inclination rate is about -0.0106 that is not dependent on the aging rate. On the other hand the capacitance is increased depending on the aging rate, so the capacitance characteristics of the oil could be applied to the diagnostic technique.

본 논문은 권선내부에 온도계가 설치된 지상변압기를 제작하여 부하운전에 따른 배전용 변압기의 온도상승 특성과 절연유의 유전특성 변화를 관찰하였다. 관찰결과 배전용변압기의 경우 과열점은 세 권선 중 두개의 권선이 접하고 권선의 약 2/3 높이에 위치하고 있으며, 과열점과 절연유 상부 간에 약 $17[^{\circ}C]$의 일정한 온도차를 확인할 수 있었다. 또한 절연유의 정전용량특성은 온도와 선형적인 관계로 감소하는 특성을 보이며, 그 기울기는 열화율과 무관하게 -0.0106의 일정한 값을 관찰할 수 있었다. 이 결과는 수명손실의 정확한 계산과 열화진단을 위한 기구로 활용할 수 있을 것이다.

Keywords

References

  1. IEEE std C57.101-1987, 'The Statistical analysis of thermal life test data'
  2. IEEE std C57.91-1995, 'IEEE Guide for Loading Mineral-Oil-Immersed Transformers'
  3. Tapan K. Saha, 'Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers,' IEEE trans on Dielectrics and Electrical Insulation, Vol. 10, No. 5, pp. 903-917, October 2003 https://doi.org/10.1109/TDEI.2003.1237337
  4. Walter S.Zaengl, 'Dielectric Spectroscopy in Time and Frequency Domain for HV Power Equipment, Part 1:Theoretical Considerations', IEEE Electrical Insulation Magazine, Vol. 19, No. 5, pp. 5-19, Sept/Oct 2003
  5. R.M.Morais, W.A.Mannheimer, M.Carballeira, J.C.Noualhaguet, 'Furfural Analysis for Assessing Degradation of Thermally Upgraded Papers in Transformer Insulation', IEEE Trans. Dielec. and Elect. Insul., Vol. 6, No. 2, pp. 159-163, April 1999 https://doi.org/10.1109/94.765905
  6. M.Ali, C.Eley, A.M.Emsley, R.Heywood, and X.Xaio, 'Measuring and Understanding the Ageing of Kraft Insulating Paper in Power Transformers', IEEE Elect. Insul. Magazine, pp. 28-34, 1996
  7. R.Batruni, R.C.Degeneff, M.A.Lebow, 'Determining the Effect of Thermal on the Remaining Useful Life of A Power Transformer from Its Impedance Versus Frequency Characteristic', IEEE Trans. Power Delivery, Vol. 11, No. 3, pp. 1385-1390, July 1996 https://doi.org/10.1109/61.517496
  8. A.M.Emsley and G.C.Stevens, 'Review of Chemical Indicators of Degradation of Cellulosic Electrical Paper Insulation in Oil-filled Transformers', IEE Proc. Sci. Meas. Tech., Vol. 141, pp.324-334, 1994 https://doi.org/10.1049/ip-smt:19949957
  9. 한전구매시방서 RS 147-170$\sim$190, '표준형 지상변압기', 2005. 11
  10. T.S.R Murthy, U.Yugandhar, S.C.Gupta, A.Bhoomaiah & J.S.Kuntia, 'Study on the Effect of Impulse Voltage Withstandability on the Thermally-aged Transformer Paper', Conference Record of the 2004 IEEE International Symposium on Electrical Insulation, Indianapolis, USA, pp.38-41, 19-22 September 2004
  11. '변압기 절연유 열화센서 진단용 계측기 개발연구' 최종보고서, 과학기술처, 1994
  12. C.T.Dervos, C.D.Paraskevas, P.Skafidas, 'Dielectric Characterization of Power Transforemer Oils as a Diagnostic Life Prediction Method,' IEEE Electrical Insulation Magazine, Vol. 21, No. 1, pp. 11-19, Jan/Feb 2005 https://doi.org/10.1109/MEI.2005.1389266