On-line Tests of on the Yang-Yang Pumped Storage Plant for the Reactive Power Limits and the OEL Dynamics

양양양수 온라인 무효전력 운전범위 시험과 과여자제한기(OEL) 동특성 시험

  • 김동준 (한국전기연구원 전력연구단 전력기술팀) ;
  • 문영환 (한국전기연구원 전력연구단)
  • Published : 2007.08.01

Abstract

This paper describes the tests on the reactive power output limit and the Over-Excitation Limiter (OEL) dynamics of a generation unit. The suggested test methods on reactive limit can identify the allowable maximum/minimum reactive power at 100% rated MW in the steady-state unit operation condition. The on-line OEL test method can identify the time characteristics of OEL with the generation output at 50% of the rated MW. These methods are validated by applying to four Yang-Yang pumped storage units with 282 rated MVA each.

Keywords

References

  1. Dmitry N. Kosterev, Carson W. Taylor, William a. Mittelstadt, Model Validation for the August 10, 1996 WSCC System Outage, IEEE Transactions on Power Systems, Vol. 14, No.3, August 1999
  2. U.S.-Canada Power System Outage Task Force, 'Final report on the August 14, 2003 blackout in the United States and Canada: Causes and recommendations,' Apr. 5, 2004
  3. 한국중부발전(주) 양양양수발전소, 양양양수 3호기 발전기/제어계 특성시험 및 모델정수 도출, 최종보고서, 2006. 8. 한국전기연구원
  4. 한국중부발전(주) 양양양수발전소, 양양양수 4호기 발전기/제어계 특성시험 및 모델정수 도출, 최종보고서, 2006. 8. 한국전기연구원
  5. 한국전력거래소, 발전기 안정도 해석 파라메터 도출 및 검증기법 표준화 연구, 최종보고서, 2006. 8, 한국전기연구원
  6. Test guidelines for synchronous unit dynamic testing and model validation, Feb. 1997, WSCC
  7. PSS/E Ver. 29, Program Operation Manual I, II, 2002