초록
This paper describes the tests on the reactive power output limit and the Over-Excitation Limiter (OEL) dynamics of a generation unit. The suggested test methods on reactive limit can identify the allowable maximum/minimum reactive power at 100% rated MW in the steady-state unit operation condition. The on-line OEL test method can identify the time characteristics of OEL with the generation output at 50% of the rated MW. These methods are validated by applying to four Yang-Yang pumped storage units with 282 rated MVA each.