This study aims to evaluate the illuminance performance of sloped light guide with automated venetian blind systems. For the purpose, a mock-up model was constructed as a prototype of Korean office building with $12.0m{\times}7.3m{\times}3.7m$ ($w{\times}d{\times}h$) and south facing side-window mounted between the clerestory window($2.0m^2$) and the view window($5.6m^2$). The light guide of 1.28m deepth and $29^{\circ}$ tilted angle, is covered with 0.6mm galvanized steel sheet and 97% reflective film. To protect the room from low solar angle, a blind systems, 0.15m deepth and $30^{\circ}$ automated slat angle was installed. To assess illuminance performance, the totally 37 measuring points for illuminance were monitored. For the detailed analysis, photometric sensors were installed at work-plane (8 points), wall (7 points), ceiling (3points), and exterior horizontal illuminance (1 point) respectively. The performance was measured under clear sky and is monitored by Agilent data logger, photometric sensor Li-cor and the Radiant Imaging ProMetric 1400. Comparisons of light factor and uniformity are discussed.