Abstract
A recently developed methods for on-site calibration of the current transformer (CT) comparator system have been reviewed in the paper. The method utilizes several traveling standards, which consist of the CT, non-reactive standard resistors, wide ratio error CT, and shunt resistors. The traveling CT is used for absolute evaluation of a standard CT belonging to industry. The non-reactive standard resistors and a wide ratio error CT are used for the linearity check of errors in the current comparator. The shunt resistors are used for evaluation of CT burden of industry.