Abstract
This paper proposes a new algorithm to find optimal location of open switches connecting feeders in distribuion system. In order to enhance power system reliability by minimizing outage area in case of fault, the load balance among the facilities such as transformers and feeders is considered to optimize. The combination of optimal position of normal open switches can be found by moving tie along the direct path connecting two feeders related to the open switch while the whole optimization problem is separated into many small problems. The proposed algorithm is shown by case study results that, it is simple and takes short calculation time to apply to the DAS (Distribution Automation System) in KEPCO (Korea Electric Power Cooperation).