A Study on Changes in Indoor Air Pollution by Educational Activities -Centering on Newly-Established Elementary Schools-

교육활동에 따른 실내오염도 변화에 관한 연구 -신설 초등학교를 중심으로-

  • 전석진 (서울특별시교육청 학교체육보건과)
  • Published : 2007.12.31

Abstract

The purpose of this study is to measure and analyze primary causes of indoor air pollution, including carbon dioxide, minute dust, and total volatile organic compounds, for each room before the beginning of a class through the time of discharge after the end of the class in general classrooms, computer rooms, and science rooms of three newly-established schools that opened in 2006, examine properties of indoor air environment in each room by educational activities at school, and determine effective management schemes; the results of this study can be summarized as follows: 1) As for implications for each item found in the mean for each place, since minute dust (PM10) was more likely to occur in time slots full of students' activities, such as a traveling class and a recess, than in the middle of a class and could be expected fully, it is necessary to make a scheme for cleaning in order to reduce minute dust within a room, for example, by usually using a vacuum cleaner indoors. 2) While carbon dioxide was expected to vary with the differences in the amount of breath between higher-graders and lower-graders in a general classroom but showed insignificant difference by grades, showing differences in pollution by four times at a maximum according to the opening of a window as expected, it is necessary to implement artificial or natural ventilation and take a positive measure, for example, by presenting a concrete ventilation scheme, in order to improve indoor air pollution at a room practice. 3) Total volatile organic compounds were found to exceed the standard by more than twice in general classrooms, science rooms, and computer rooms of the schools because of building materials, furnitures including desks and chairs, panels and boards for environment beautification, and items which could be detected even from students' clothes; while a field directly-reading tool was used, obtaining high reliability for the results, it is necessary to apply an analytical method based on process test separately for actual correct measurement if a significantly great amount of total volatile organic compounds appear as compared with other schools due to measuring expenses and consecutive measurements. 4) Since formaldehyde (HCHO) was generally found to exceed the standard in general classrooms, science rooms, and computer rooms, it is necessary to establish and operate a ventilator during a class in a computer room which requires airtightness and a science room in which an organic compound should be used for a class.

Keywords