Construction of On-Site Calibration Facilities of 66 kV Voltage Transformer Comparator System

66kV급 전압변성기 비교측정 장치의 현장 평가설비 구축

  • Published : 2007.07.01

Abstract

A recently developed methods for the on-site calibration of the voltage transformer (VT) comparator system have been reviewed in the paper. The method utilizes the several traveling standards consisting of the VT, the non-reactive standard resistors, the wide ratio error VT, and the decade resistors. The VT is used for the absolute evaluation of a standard VT belonging to the industry. The non-reactive standard resistor and wide ratio error VT are used for the linearity check of errors in the voltage comparator of the industry. The decade resistors are used for evaluation of a VT burden of the industry.