Abstract
Combustion characteristics and toxicity of combustion gas of wallpaper samples were analyzed to evaluate the fire risk of wallpaper furnished in living space. In this study ash residue ratio was measured with high temperature electric furnace, and thermal analysis was carried out with TGA. Combustion time and smoke concentration were measured with cone heater and combustion gas analyzer. Smoke density of samples was measured using smoke chamber of ASTM E 662. The experimental results were showed as followings. Pyrolysis of silk wallpaper started at lower temperature compared to the other samples. It means that the silk wallpaper can be ignited at low heat flux and will have more fire risk than the others. Ignition time by radiation heat flux of silk wallpaper is shorter compared to the other samples, so evacuation time must be reduced. In the case of vinyl coated silk wall paper, carbon mono oxide concentration is the highest and the toxicity and damage effect to consciousness was stronger compared to the other samples. Smoke density of silk wall paper and fire retardant mixed coated silk wall paper were very high due to vinyl coating.
주거공간에 사용되는 벽지의 화재 위험성을 평가하기 위하여 몇 종류의 벽지 시료에 대한 연소특성과 연소가스의 독성을 분석하였다. 본 연구에서 재의 잔량은 고온의 전기로를 이용하여 측정하였으며 TGA를 이용하여 열적 특성을 분석하였다. 연소시간과 연기농도의 측정은 콘히터와 가스분석계를 사용하였고 연기밀도는 ASTM E662의 장치를 이용하였다. 실험결과 실크벽지는 다른 벽지에 비해 낮은 온도에서 열분해가 시작되었는데 이는 실크벽지가 낮은 열유속(heat flux)에서도 착화될 수 있으므로 다른 벽지보다 화재 위험성이 높다. 실크벽지의 복사 열유속에 의한 착화시간은 다른 시료들에 비해 짧아서 화재 시 피난 시간이 짧아져야 하며 비닐이 코팅된 실크벽지 연소 시 일산화탄소의 발생 농도가 가장 높아서 독성의 위험이 높을 것으로 보인다. 실크벽지와 실크방염 벽지의 비닐 코팅으로 연기밀도가 높게 나타났다.