공조기가 설치된 고분 내에서의 열 및 음 환경 평가

Evaluation of the Thermal and Noise Environment in an Ancient Tomb installed a Duct-type HVAC System

  • 박진양 (공주대학교 기계공학과 대학원) ;
  • 전희호 (공주대학교 기계공학과 대학원) ;
  • 전용두 (공주대학교 기계자동차공학부) ;
  • 이금배 (공주대학교 기계자동차공학부)
  • Park, Jin-Yang (Graduate School, Kongju National University) ;
  • Jun, Hee-Ho (Graduate School, Kongju National University) ;
  • Jun, Yong-Du (Department of Mechanical and Automotive Engineering, Kongju National University) ;
  • Lee, Kum-Bae (Department of Mechanical and Automotive Engineering, Kongju National University)
  • 발행 : 2007.03.10

초록

Opening an ancient tomb interior can deal fair damage for preservation in long period because of high moisture. In this study, a duct-type HVAC system was installed to preserve an ancient tomb and temperature and humidity was measured to analyze heat environment. Armhole was measured to search whether an ancient tomb receives effects of vibration caused by a duct-type HVAC system. According to the measured data, temperature in an ancient tomb is kept adaptively in conservation regardless of a duct-type HVAC system installation when it rains in summer. The other side, humidity is kept adaptively in conservation when installed duct-type HVAC system. But when it is in natural state, a lot of humidity by dew condensation phenomena. So it needs a duct-type system for an ancient tomb conservation. In the case of vibration, measurement value of 3 satisfy control but Germanic DIN 4150 does not satisfy. Therefore, equip must be such that it can prevent vibration for safety.

키워드

참고문헌

  1. Lee, J. K. and Song, T. H., 1999, Experimental investigation of dew formation and heat transfer in the original upper structure of Sokkuram grotto, SAREK 1999 Summer Annual Conference, pp. 68-76
  2. Lim, K. H., Jeong, S. U., Lim, Y. G., Kong, S. H., Moon, S. H. and Yoon, H. K., 1998, An experimental study on the Sokkuram cave temple dome's indoor environment of miniature model in winter season, SAREK 1998 Summer Annual Conference, pp.187-190
  3. Suh, M. C., Lee, N. S., Choi, S. W., Kim, G. H., Jeong, S. M. and Lee, K. B., 1998, In-situ Status and conservational strategy of the Muryong royal tomb, the Songsanri tomb No.5 and the Songsanri tomb No.6 of Baekje dynasty, The Research Institute of Bas. Sci. Kongju Nat'l, Univ., The Journal of Natural Science, Vol. 7, pp.147-161
  4. Jun, Y. D., Lee, K. B., Kim, H. G. and Ko, S. B., 2004, Temperature and humidity distribution inside Sinkwan-ri tomb, SAREK 2004 Winter Annual Conference, pp.601-607
  5. Jun, Y. D., Lee, K. B., Ko, S. B. and Kim, H. G., 2004, Temperature and humidity difference properties inside Shinkwan-ri tomb for different seasons, SAREK 2004 Winter Annual Conference, pp.253-258
  6. Thomson, G., 1986, The museum environment, 2nd ed., Butterworth-Heinemann, London, p.88
  7. Song, J. T., 1998, HVAC system applied to storage of the national museum of Korea, SAREK 1998 Summer Annual Conference, pp. 1577-1584
  8. Web site: www.unovics.co.kr
  9. SAREK, 2001, SAREK Handbook, Vol. 2, Air-Conditioning, pp. 1.3-1.4
  10. Lee, K. B., 2005. Development of an Optimized HVAC System for Ancient Tombs Conservation, Report of Kongju Nat'l, Univ., pp.149-156
  11. The Ministry of Environment Notice, 2003, The Noise and a Vibration Process Test Way, Vol. 2003-221, Korea
  12. Korean Industrial Standard, KSA 0603, 1988, A Vibration Level Measurement Way