Abstract
In this paper, the performance characteristics of heat pump system using a new refrigerant subcooling system designed for the study, are introduced. The new heat pump system have the ice storage tank at the outlet of condenser. The experimental apparatus is a well-instrumented water/water heat pump which consisted of working fluid loop, coolant loop, and ice storage tank. The experiment parameters of subcooling ranged as the evaporating temperature from $-5^{\circ}C$ to $8^{\circ}C$, the condensing temperature from $30^{\circ}C$ to $35^{\circ}C$. The test of the ice storage was carried out at evaporating temperature of $-10^{\circ}C$ and the ice storage mode is Ice-On-Coil type. The working fluid was R-22 and the storage materials were city-water. The test results obtained were as follows; The refrigerant mass flow rate and compressor shaft power were unchanged by the degrees of subcooling, that is, they were independent of degrees of subcooling. The cooling capacity of the new heat pump system increase as the evaporating temperature and subcooling degrees increase and is higher by $25{\sim}30%$, compared to the normal heat pump system. The COP of the new heat pump system increases as the degrees of subcooling and evaporating temperature increase and is higher by 28% than that of the normal heat pump system.