Study on the Development of Heat Recovery Ventilator

폐열회수형 환기장치 개발에 관한 연구

  • Received : 2007.06.28
  • Accepted : 2007.12.05
  • Published : 2007.12.31

Abstract

To evaluate the performance of heat exchanger with rotating porous plates, the experimental investigation was carried out under various conditions. With an equal interval of 18 mm inside the heat exchanger, the rotating porous plates are mounted. The hot and cold airs enter at opposite ends of heat exchanger and exchange heat each other. In order to measure the temperature distribution of the hot air side inside heat exchanger, the thermocouples are inserted between the plates. The first location of thermocouple is 10 mm downstream from the inlet of heat exchanger, and succeeding ten locations are aligned at an equal interval of 18 mm. As a result of the measurement, the temperature distribution inside heat exchanger was constant as the hot air temperature of inlet is low. It was found that the heat transfer rate does not depend on the variation of RPM at the lower temperature of inlet. The heat transfer rate at the higher temperature of inlet increased a little with the increase in RPM.

Keywords

References

  1. 송두삼, 조왕희, 고현준, 윤인철, 이기섭(2005). 시뮬레이션을 통한 환기방식별 실내공기질 제어 및 냉난방 부하 특성의 비교, 대한설비공학회 하계학술발표대회 논문집, 83-90
  2. 이정재, 이시환, 박성관, 오상경(2004). 실험을 통한 열교환 환기장치 실험규격의 민감도 분석, 대한설비공학회 하계학술발표대회 논문집, 195-200
  3. 전용두, 이금배, 고석보, 전희호, 박진양, 윤영묵(2005). 연도가스 열회수용 유동층 열교환기 설계, 대한설비공학회 하계학술발표대회 논문집, 546-553
  4. 조진표, 김내현, 최동식(2004). 활성탄이 침착된 전열교환기 성능평가, 대한설비공학회 동계학술발표대회 논문집, 666-670
  5. Incropera, F. P., and DeWitt, D. P.(1996). Fundamentals of Heat and Mass Transfer, Wiley, Fourth Edition
  6. Webb, R. L.(1996). Principles of Enhanced Heat Transfer, Wiley