Performance and Heat transfer Characteristics of Louver Fin-tube Heat Exchanger for Simultaneous Cooling/Heating Heat Pump

동시 냉난방 히트펌프용 루버핀-관 열교환기 성능 및 전열특성 실험연구

  • Published : 2007.12.31

Abstract

An experimental study has been performed to investigate the performance and heat transfer characteristics of the heat exchanger for simultaneous cooling/heating heat pump. The heat transfer performance was measured using an air-enthalpy calorimeter and a constant temperature water bath, to obtain the performance evaluation and analysis of a fined tube heat exchanger. Six finned tube heat exchangers with louver fin were tested under a heating condition. Air-side heat transfer and friction were presented in terms of j-factor and f-factor. The heat transfer coefficient increased with decreasing the fin pitch, j-factor and f-factor on the fin pitch and the number of tube rows decreased with increasing Reair.

본 연구에서는 동시 냉난방 히트펌프용 열교환기의 성능평가 및 설계해석 기술의 확보를 위해 난방운전 온도조건에서 6종의 루버핀-관 열교환기의 공기측 열전달특성 및 마찰특성을 실험을 통하여 조사하였다. 실험을 위해 공기엔탈피방식의 칼로리미터와 항온수조를 이용하였다. 전열량의 증가는 핀피치보다 열수에 의해 더 크게 나타났고, 핀피치가 작을수록 열전달계수는 더 높았다. 또한 핀피치가 작을수록 열수증가에 의한 열전달계수의 증가폭이 커졌다. 핀피치와 열수변화에 대한 j-계수와 f-계수는 레이놀즈 수가 증가할수록 감소하였고, 레이놀즈 수 400부근의 영역에서 역전현상이 존재하였다.

Keywords