Journal of the Korean Society for Geothermal and Hydrothermal Energy (한국지열·수열에너지학회논문집)
- Volume 3 Issue 1
- /
- Pages.11-16
- /
- 2007
- /
- 2799-4783(pISSN)
- /
- 2799-4805(eISSN)
The Comparison of the EWT&LWT between Field Measurement and CFD of Vertical-type Geothermal Heat Exchanger
수직형 지열교환기의 입.출구온도에 대한 실측과 CFD 결과 비교
- Woo, Sang-Woo (Graduate School, Korea Maritime University) ;
- Kim, Joong-Hun (Research of Technology, Samsung Engineering & Construction) ;
- Shin, Seung-Ho (Research of Technology, Samsung Engineering & Construction) ;
- Hwang, Kwang-Il (Dept. of Mechanical and Information Engineering, Korea Maritime University)
- Published : 2007.06.01
Abstract
The purpose of this study is to use the CFD(Computational Fluid Dynamics) method for the ground source heat pump(GSHP) system with vertical U-tube ground heat exchangers. In order to predict LWT(leaving water temperature) in the length of time, This simulation is used by utilizing FLUENT which is commercial CFD code. It was performed by based on four boreholes in the field. Comparing with the results of CFD and field measurement for LWT, the results of CFD was presented very good agreement with 1.0% average difference.
Keywords