A study on the vehicle fire property using the large scale calorimeter

대형칼로리미터를 이용한 차량 화재 특성에 관한 연구

  • Published : 2007.12.28

Abstract

The reduced scale fire test provides basic data but it is not enough to analysis real fire problem directly because there is no exact analogy theory between a real fire and the reduced scale model. Therefore we have developed the large scale calorimeter in order to the real scale fire test. This advanced large scale calorimeter used for physical properties such as a heat release rate, based upon consumption of $O_2$ method. Using this large scale calorimeter, we cameo out the real scale vehicle fire test in order to evaluation for heat release rate. We obtained the calculated result for HRR $2.3{\sim}3.4\;MW$ and this result is very similar to the PIARC candidate HRR. It is approve that this facility has the reliability and it is capable of applying to the advance fire research in the future.

터널 화재와 관련된 축소모형실험연구는 기본적인 데이터는 제공할 수 있지만, 축소모형과 실물화재간의 정확한 이론적 상사관계가 정립되어 있지 않기 때문에 실물화재에 대한 직접적인 분석을 하기에는 어려움이 따른다. 이에 산소소모율법을 적용하여 열방출율과 같은 물리량의 측정이 가능한 실물화재실험장치인 대형칼로리미터를 개발하였다. 이를 이용하여 차량의 화재시 열방출율을 측정하기 위한 실물실험을 실시하였으며, 그 결과 차량의 열방출율은 $2.3{\sim}3.4\;MW$로 측정되었다. 이는 PIARC에서 권고하는 차량의 열방출율과 유사한 범위로서 개발된 실물화재평가장치의 신뢰성을 확인할 수 있음은 물론이고 향후 관련 연구에 매우 유용하게 이용될 수 있을 것이다.

Keywords