DOI QR코드

DOI QR Code

A Study on the Short Circuit Characteristic of Metallic Stabilizer Free Coated Conductor for FCL Application

  • Park, Dong-Keun (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Kim, Min-Jae (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Yang, Seong-Eun (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Kim, Young-Jae (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Chang, Ki-Sung (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Na, Jin-Bae (Department of Electrical and Electronic Eng., Yonsei University) ;
  • Ko, Tae-Kuk (Department of Electrical and Electronic Eng., Yonsei University)
  • 발행 : 2007.11.30

초록

As power demands increase, development of the superconducting fault current limiter (SFCL) is being watched with interest. Many types of SFCLs using various superconducting materials have been developed. Especially, the FCL using coated conductor (CC) has been investigated actively at present. CCs have many advantages for the FCL application. YBCO materials used in CCs have a high n-value, and it is relatively easy to choose a matrix of the CC for high resistivity. If the CC has high resistivity, high voltage can be applied to the CC. Then total length of the CC used in SFCL, which has effects on total price and volume of the SFCL, can be reduced. Short circuit tests of two different types of CCs in the liquid nitrogen bath and its sub-cooled condition were performed and analyzed. An effect of high resistivity of the CC and cooling methods on fault current limiting characteristics could be verified in this paper.

키워드

참고문헌

  1. Kalsi, S.S., Malozemoff, A, "HTS fault current limiter concept," IEEE Power Engineering Society General Meeting, 2004, vol. 2, pp. 1426-1430, 2004
  2. D. K. Park, M. C. Ahn, S. E. Yang, Y. S. Yoon, B.-Y. Seok, C. Lee, H.-M. Chang, and T. K. Ko, "Development of 220 V/300 A Class Non-inductive Winding Type Fault Current Limiter Using 2G HTS Wire," IEEE Trans. Appl. Supercond., vol. 17, pp. 1855-1858, 2007 https://doi.org/10.1109/TASC.2007.898130
  3. M. C. Ahn, D. K. Park, S. E. Yang, Y. J. Kim, H. M. Kim, H. Kang, K. Nam, B.-Y. Seok, J.-W. Park, and T. K. Ko, "A Study on the Design of the Stabilizer of Coated Conductor for Applying to SFCL," IEEE Trans. Appl. Supercond., vol. 17, pp. 1863-1866, 2007 https://doi.org/10.1109/TASC.2007.897756
  4. K. Nam, H. Kang, C. Lee, T. K. Ko, and B. Y. Seok, "Visualization study on boiling of nitrogen during quench for fault current limiter applications," IEEE Trans. Appl. Supercond., vol. 16, pp. 727-730, 2006 https://doi.org/10.1109/TASC.2005.869669
  5. K. Nam, C. Lee, D. K. Park, T. K. Ko, B.-Y. Seok, "Thermal and Electrical Analysis of Coated Conductor Under AC Over-Current," IEEE Trans. Appl. Supercond., vol. 17, pp. 1923-1926, 2007 https://doi.org/10.1109/TASC.2007.897199
  6. M. J. Kim, M. C. Ahn, S. E. Yang, D. K. Park, Y. J. Kim, T. K. Ko, C. Lee, and B.-Y. Seok, "Determination of Maximum Permissible Temperature Rise Considering Repetitive Over-Current Characteristics of YBCO Coated Conductors," 20th International Conference on Magnet Technology, Philadelphia, Pennsylvania USA, August 27-31, 2007