A Study on Utilization Ratio and Operation of Transmission Lines

송전선로의 이용률 평가 및 합리적 운영에 관한 연구

  • 김동민 (한양대 공대 전기공학과) ;
  • 배인수 (한양대 공대 전기공학과) ;
  • 조종만 (전력거래소 계통운영처) ;
  • 김진오 (한양대 공대 전기공학과)
  • Published : 2006.10.01

Abstract

This paper describes the concepts of Static Line Rating (SLR) and Dynamic Line Rating (DLR) and the computational methods to demonstrate them. Calculation of the line capacity needs the heat balance equation which is also used for computing the reduced tension in terms of line aging. SLR is calculated with the data from the worst condition of weather throughout the year. Even now, the utilization ratio is obtained from this SLR data in Korea. DLR is the improved method compared to SLR. A process for DLR reveals not only improved line ratings but also more accurate allowed line ratings based on line aging and real time conditions of weather. In order to reflect overhead transmission line aging in DLR, this paper proposes the method that considers the amount of decreased tension since the lines have been installed. Therefore, the continuous allowed temperature for remaining life time is newly acquired. In order to forecast DLR, this paper uses weather forecast models, and applies the concept of Thermal Overload Risk Probability (TORP). Then, the new concept of Dynamic Utilization Ratio (DUR) is defined, replacing Static Utilization Ratio (SUR). For the case study, the two main transmission lines which are responsible for the north bound power flow in the Seoul metropolitan area are chosen for computing line rating and utilization ratio. And then line rating and utilization ratio are analyzed for each transmission line, so that comparison of the present and estimated utilization ratios becomes available. Finally, this paper proves the validity of predictive DUR as the objective index, with simulations of emergency state caused by system outages, overload and so on.

Keywords

References

  1. A. Chakrabarti and A.K. Mukhopadhyay 'Operating problems in longitudinal power supply systems', TENCON '89. Fourth IEEE Region 10 International Conference, Vol. 22-24, pp. 932-935, 1989 https://doi.org/10.1109/TENCON.1989.177084
  2. 송전설계기준 제개정 및 보완연구(최종보고서), 한전전력연구원, pp. 207, 2001. 5
  3. D.A. Douglass and A.A Edris 'Real-time monitoring and dynamic thermal rating of power transmission circuits', IEEE Transaction on Power Delivery, Vol. 11, No. 3, pp. 1407-1418, 1996 https://doi.org/10.1109/61.517499
  4. T.O. Seppa, 'Increasing transmission capacity by real time monitoring', 2002 IEEE Power Engineering Society Winter Meeting , Vol. 2, pp. 1208-1211, 2002 https://doi.org/10.1109/PESW.2002.985201
  5. 'IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors', IEEE Std 738, 1993
  6. 조종만, 배인수, 김동민, 김진오 : '확률적 기법을 이용한 가공 송전선로 도체의 장력감소 계산', 대한전기학회 추계 학술대회 논문집, 대한전기학회, 전남대학교, 2005. 11. 18-19, pp. 226-229
  7. 가공송전의 전류용량, 일본전기학회 기술보고, 제 660호, 1997
  8. N.P. Schnidt 'Comparison between IEEE and CIGRE ampacity standards', IEEE Transaction on Power Delivery, Vol. 14, No. 4, pp. 1555-1559, 1999 https://doi.org/10.1109/61.796253
  9. ACSR 전선수명 예측시스템 개발, 한전 전력연구원, PP. 18, 2000.1
  10. 가공송전운영업무기준, 한전, PP. 110, 2006.5
  11. 김동민, 배인수, 조종만, 김진오, 장경 '시계열 기상모델을 이용한 열적 위험확률 기반 동적 송전용량의 예측', 전기학회논문지 제 55권 7호 pp. 273-280, 2006