Effect of Harmonics on Residual Current Protective Devices

고조파가 누전차단기에 미치는 영향

  • 전정채 (한국전기안전공사 전기안전연구원) ;
  • 이상익 (한국전기안전공사 전기안전연구원) ;
  • 유재근 (한국전기안전공사 전기안전연구원)
  • Published : 2006.03.31

Abstract

Tripping of residual current protective devices(RCPDs) caused by harmonics has been continuously reported, but no literature is available on the behavior of RCPDs caused by harmonics. This paper, in order to find out the effects of harmonics on RCPDs, investigated the present condition on malfunction of RCPDs and measured harmonics at buildings where nuisance tripping of RCPDs was often occurred. Also, the operational characteristics of RCPDs were tested by the harmonics synthesizer that can generate distorted waveform. Results of experiment detected that there was minimum tripping current of RCPDs when third harmonic added to the fundamental frequency. And it was found that the leakage current to cause tripping of RCPDs increased with more higher order harmonics added to the fundamental frequency.

고조파에 의한 누전차단기 동작이 계속적으로 보고되어 왔으나 누전차단기 동작을 설명할 수 있는 자료가 없는 실정이다. 본 논문에서는 누전차단기에 대한 고조파 영향을 규명하기 위해 누전차단기 오동작 현황에 대한 조사 및 누전차단기 원인불명 동작이 자주 발생하는 건물에서 고조파를 측정 및 분석하였다. 또한 왜곡된 파형을 발생시킬 수 있는 고조파 합성장치를 이용하여 누전차단기 동작 특성을 시험하였다. 시험결과 3차 고조파가 기본파에 합성되었을 때 가장 작은 값의 누설전류에 누전 차단기가 동작되었고 기본파에 더해진 고조파 차수가 증가할 수 록 누전차단기 동작전류는 증가하였다.

Keywords

References

  1. KSC 4613 : 누전차단기, pp. 1-22, 2002
  2. 대한전기협회, '내선규졍', pp. 134-138, 2003
  3. KSC/IEC 61009-1 : 가정용 및 이와 유사한 설비의 과전류 보호용 누전 차단기-제1부 : 일반요구사항, pp. 1-100, 2002
  4. IEC 61008-1 : Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses(RCCBs)-Part 1 : General, pp. 1-255, 2002
  5. IEC 61543 : Residual current operated protective devices(RCDs) for household and similar uses-Electromagnetic compatibility, 1-19, 1995