Abstract
The disastrous accident happens and the economic loss comes into being at the power facilities that used a industry site, if the fault comes into being. This paper experiments the partial discharge in the GIS used a $SF_6$ insulation gas by the pressure change. We studied the influence of particles at the partial discharge in a $SF_6$ gas. We use UHF method and measure the partial discharge signal radiation electromagnetic waves and to be happened at the $SF_6$. And we analyzed the influence on the $SF_6$ gas to have the particles which the partial discharge analyzes a spectrum of the radiated electromagnetic waves and comes out. The paper results aided the prevention of breakdown accident that happened by particles when an inside pressure changes at the GIS & the power facilities used $SF_6$ gas.
산업현장에서 많이 사용되고 있는 전력기기에 결함이 발생하면 치명적인 사고로 진전되어 경제적, 인적 손실이 발생될 수가 있다. 본 논문은 GIS에 사용되는 절연가스인 $SF_6$의 압력 변화에 따른 부분방전을 모의하고, 발생되는 부분방전 신호를 절연 진단 방법 중 하나인 UHF법을 이용하여 부분방전 시 방사되는 방사전자파의 스펙트럼을 분석해 금속 이물질이 $SF_6$가스 부분방전에 미치는 영향을 측정하였다. 이러한 연구는 현장 GIS 및 $SF_6$가스절연 전력설비에서 내부압력 변화 시 금속 이물질에 의해 발생되는 절연파괴 사고의 방지에 중요한 역할을 할 것으로 사료된다.