A Comparative Study of The PD Pattern Analysis Based on PRPD and CAPD for The Diagnosis of Gas Insulated Transformer

GITr(Gas Insulated Transformer) 내부에 발생되는 PD 신호의 패턴분석을 위한 PRPD와 CAPD 적용결과 비교

  • 정승용 (한양대 공대 전자전기제어계측과) ;
  • 구자윤 (한양대 공대 전자전기제어계측과)
  • Published : 2006.06.01

Abstract

Partial Discharge (PD) phenomena occurred by different nature of insulating defects has been regarded as a random process by which Phase Resolved Partial Discharge Analysis(PRPDA) has been proposed and then commercially accepted for the diagnosis of the power apparatus since more than three decades. Moreover, for the same purpose, a novel approach based on the Chaotic Analysis(CAPD) has been proposed since 2000, in which Partial Discharge(PD) phenomena is suggested to be considered as a deterministic dynamical process. In this work, for the diagnosis of Gas Insulated Transformer(GITr), four different types of specimen were fabricated as a model of the possible defects that might possibly cause its sudden failures such as turn to turn insulation, inter coil insulation, free moving particle and protrusion. For this purpose, these defects are introduced into the Gas Insulated Transformer(GITr) mock-up and experimental investigations have been carried out in order to analyze the related Partial Discharge(PD) patterns by means of both Phase Resolved Partial Discharge Analysis(PRPDA) and Chaotic Analysis(CAPD) respectively and then their comparisons are made systematically.

Keywords

References

  1. Edward Gluski, Computer-Aided Recognition of Partial Discharges Using Statistical Tools, Delft University Press, Delft, Netherlands, 1991
  2. Okamoto, T., Tanaka T., 'Novel Partial Discharge Measurement Computer-aided Measurement Systems', IEEE Trans. on Electrical Insulation, Vol. 21, pp. 1015-1019, 1986 https://doi.org/10.1109/TEI.1986.349017
  3. Andrej KRIVDA, Recognition of Discharges-Discrimination and Classification, Delft University Press, Delft, Netherlands, 1995
  4. M. Hoof and R. Patsch, 'Pulse Sequence Analysis : A New Method for Investigating the Physics of PD-induced Ageing', IEE Proc-Sci. Meas. Technol., Vol. 142, No. 1, pp. 95-101, 1995 https://doi.org/10.1049/ip-smt:19951563
  5. J. Y. Koo, Y. S. Lim, W. J. Kang, and Y. M. Chang, 'A Possible Application of the PD Detection Technique using electro-optic Pockels Cell with nonlinear characteristic analysis on the PD signals', IEEE-CEIDP 2000, pp.531-534, 2000 https://doi.org/10.1109/CEIDP.2000.884015
  6. Y.S.Lim , J.Y.Koo , 'Comparative Analysis of Partial Discharge Pattern from Different Artificial Defects by Means of Conventional Phase-Resolved Partial Discharge Analysis and a Novel Chaotic Analysis of Partial Discharge', Journal of the Korean Physical Society, Vol.42, No6, pp 755-764 June 2003