Abstract
In the operation of large capacity hydro generators, it's a very important thing that to minimize several kind of electrical trouble and accident. In order to overcome these problems, the on-line and off-line partial discharge (PD) measuring method has become an important one. Nowadays, epoxy mica coupler(EMC) has been the most widely used sensors for on-line PD detection in rotating machines. This time, we have made a ceramic coupling sensor using $SrTiO_{3}$, because at present, most of sensors has high cost and difficult procedure to making. This paper deals with the electrical characteristics of a ceramic coupling sensor, which has been made to continuously measure PD activity during the operation condition for 13kV class hydro generator. And we have performed the evaluation of sensor life and reliability based on the characteristic testing. The experimental results confirm that the sensor has satisfied at electrical required performance and output characteristic for simulated input signal.