A Modified Selective Ground Relay for Ungrounded Distribution Systems

  • Nam Soon-Ryul (Next-Generation Power Technology Center(NPTC) and the Department of Electrical Engineering, Myongji University) ;
  • Kang Sang-Hee (Next-Generation Power Technology Center(NPTC) and the Department of Electrical Engineering, Myongji University) ;
  • Park Jong-Keun (School of Electrical Engineering, Seoul National University)
  • Published : 2006.03.01

Abstract

Selective ground relays (SGRs) are useful fur distinguishing a faulted feeder from the sound feeders in ungrounded systems. However, they sometimes mis-operate due to human or device errors. Particularly, the reversed polarity of zero-sequence current transducers (ZCTs) is the most frequent cause of mis-operation. This paper presents a modified SGR for reducing the probability of mis-operations caused by the reversed polarity of ZCTs. The modification is achieved by introducing an adaptive time delay, which depends on the magnitude of the zero-sequence current and the phase angle deviation from the reference. The modified SGR was successfully demonstrated on a sample ungrounded system without mis-operation.

Keywords

References

  1. T. Baldwin. and F. Renovich, 'Analysis of fault locating signals for high-impedance grounded systems,' IEEE Trans. Industry Applications, Vol. 38, no. 3, pp. 810 - 817, May-June 2002 https://doi.org/10.1109/TIA.2002.1003434
  2. Xu Bingyin; Xue Yongduan; Li Jing; and Chen Yu; 'Single phase fault detection technique based on transient current and its application in non-solid grounded network,' in Proceedings of Developments in Power System Protection 2001 Conference, pp. 141 - 144, April 2001
  3. Jun Liang; Zhihao Yun; Feifan Liu; and Yutian Liu; 'A method of fault line detection in distribution systems based on wavelets,' in Proceedings a/Power System Technology 2002 Conference, pp. 2635 2639, Oct. 2002
  4. E. T. B. Gross, 'Sensitive Fault Protection for Transmission Lines and Distribution Feeders,' AIEE Transactions, Vol. 60, pp. 968 - 972, Nov. 1941
  5. AIEE committee Report, 'Sensitive Ground Protection,' AIEE Transactions, Vol. 69, 1950, pp. 473-476
  6. S. Hanninen and M. Lehtonen, 'Method for detection and location of very high resistive earth faults,' European Trans. Electrical Power, vol. 9, no. 5, pp. 285-291, 1999 https://doi.org/10.1002/etep.4450090501
  7. Z.M. Radojevic, V.V. Terzija, and N.B. Djuric, 'Numerical algorithm for overhead lines arcing faults detection and distance and directional protection,' IEEE Trans. Power Delivery, Vol. 15, no. 1, pp. 31 37, Jan. 2000 https://doi.org/10.1109/61.847225
  8. T. Baldwin, F. Renovich, and L.F. Saunders; 'Directional ground-fault indicator for high-resistance grounded systems,' IEEE Trans. Industry Applications, Vol. 39, no. 2, pp. 325 - 332, March-April 2003 https://doi.org/10.1109/TIA.2003.808948
  9. Standards of Korea Electrical Manufactures Cooperative, KEMC 1120-1996
  10. IEEE standard inverse-time characteristic equations for overcurrent relays, IEEE Std C37 112-1996

Cited by

  1. The current limiting effects of a matrix-type SFCL according to the variations of designed parameters in the trigger and current-limiting parts vol.468, pp.15-20, 2008, https://doi.org/10.1016/j.physc.2008.05.125
  2. The Characteristic Analysis Between Flux-Coupling and Flux-Lock Type SFCL According to Variations of Turn Ratios vol.18, pp.2, 2008, https://doi.org/10.1109/TASC.2008.920637
  3. Critical Current Equalization via Neutral Lines in a Transformer-Type SFCL vol.18, pp.2, 2008, https://doi.org/10.1109/TASC.2008.920635