테이프가 있는 거친 사각채널에서 가열벽면의 수가 열전달에 미치는 효과

Effects of Number of Heating Walls on Heat Transfer in the Rough Square Channel with Twisted Tape

  • 안수환 (경상대학교 기계항공공학부, 해양산업연구소) ;
  • 김명호 (경상대학교 대학원 기게시스템공학과) ;
  • 배성택 (주식회사 태건) ;
  • 강호근 (경상대학교 해양산업연구소)
  • 발행 : 2006.08.31

초록

Surface modifications like rib-roughening and displaced insert devices like the twisted tape are commonly used in applications such as compact heat exchangers and cooling systems. In this paper, regionally averaged heat transfer distributions in square channels with twisted tape inserts and with twisted tape inserts plus interrupted ribs are respectively investigated. The square ribs are arranged to follow the trace of the twisted tape and along the flow direction defined as axial interrupted ribs. Each wall of the square channel is composed of isolated aluminum sections. Regionally averaged Nusselt number and channel averaged Nusselt number in turbulent air flows are presented for Reynold numbers from 8,900 to 29,000. We have obtained the following conclusions from the experimental study: 1) The local Nusselt number in the two-sided heated case is higher than that in the four-sided heated condition. 2) In the 4 heating wall channel with twisted tape inserts, Nusselt number based on bottom wall temperature is enhanced by 1.2 - 1.6 times if adding the axial interrupted ribs on the bottom wall only. 3) The twisted tape with interrupted ribs under the two-sided heating condition produces the highest heat transfer coefficient.

키워드