DOI QR코드

DOI QR Code

Closed-Loop Cooling System for High Field Mangets

고자기장용 자석을 위한 밀폐순환형 냉각장치

  • Published : 2006.03.01

Abstract

A closed-loop cryogenic cooling system for high field magnets is presented. This design is motivated by our recent development of cooling system for 21 tesla Fourier Transform ion Cyclotron Resonance (FT-ICR) superconducting magnets without any replenishment of cryogen. The low temperature superconducting magnets are immersed in a subcooled 1.8 K bath, which is connected hydraulically to the 4.2 K reservoir through a narrow channel. Saturated liquid helium is cooled by Joule-Thomson heat exchanger and flows through the JT valve, isenthalpically dropping its pressure to approximately 1 6 kPa, corresponding saturation temperature of 1.8 K. Helium gas exhausted from pump is now recondensed by two-stage cryocooler located after vapor purify system. The amount of cryogenic Heat loads and required mass flow rate through closed-loop are estimated by a relevant heat transfer analysis, from which dimensions of JT heat exchanger and He II heat exchanger are determined. The detailed design of cryocooler heat exchanger for helium recondensing is performed. The effect of cryogenic loads, especially superfluid heat leak through the gap of weight load relief valve, on the dimensions of cryogenic system is also investigated.

Keywords

References

  1. National Research Council, "Opportunities in high magnetic field science", National Academy of Sciences, Washington D. C., 2004, Available from: http://www.nap.edu
  2. Dixon I. R. et al.. "Performance of the ultra wide bore 900 MHz NMR magnet at the National High Magnetic Field Laboratory", IEEE Trans Appl Supercond, Vol. 15, 1334-1337, 2005 https://doi.org/10.1109/TASC.2005.849588
  3. Kiyoshi T. et al., "Operation of a 920-NHz high-resolution NMR magnet at TMI". IEEE Trans Appl Supercond, Vol. 13, 1391-1395, 2003 https://doi.org/10.1109/TASC.2003.812675
  4. Painter T. A. et al., "Conceptual design of superconducting magnet system for 21 T fourier transform ion cyclone resonance mass spectrometer", In: International Conference on Magnet Technology, September 2005, Paper#TUA30R3
  5. Choi Y.S. et al., "Conceptual design of cryogenic cooling system for 21 T ICR Magnetsmeter". In: International Conference on Magnet Technology, September 2005, Paper#WEA03PO10
  6. Ng K.C. et al., "Experimental and numerical study on a miniature Joule-Thomson cooler for steady-state characteristics, Int. J. Heat and Mass Transfer, Vol. 45, 609-618, 2002 https://doi.org/10.1016/S0017-9310(01)00165-X
  7. Ueno Y. et al., "Numerical study on characteristics of a pre-cooling He II heat exchanger", Advances in Cryogenic Engineering, Vol.49, 1039-1046, 2004
  8. Barron R.F., "Cryogenic Heat Transfer", Philadelphia, Taylor & Francis, 1999
  9. Van Sciver S.W., "Heat transfer through an extended surface containing He II", Journal of Heat Transfer, Vol.121, 142-147, 1999 https://doi.org/10.1115/1.2825927
  10. Van Sciver S.W., "Helium Cryogenics", New York, Plenum Press, 1986
  11. Gerald C.F, Wheatly P.O., "Applied Numerical Analysis", New York, Addition-Wesley, 1996
  12. Mardion G.B. et al.. "Practical data on steady state heat transport in superfluid helium at atmospheric pressure", Cryogenics, Vol.19, 45-47, 1979 https://doi.org/10.1016/0011-2275(79)90109-7
  13. Matsumoto F. et al., "Testing of superfluid-coo led 920 MHz NMR cryostat", Advances 10 Cryogenic Engineering, Vol.47, 383-390, 2002
  14. Product Catalogue of Cryomech. Model PT415, New York, 2005, Available from: http://www.cryomech.com