UHF Partial Discharge Measurement Technology using a Dual Bands Methods to have the Frequency Characteristics in GIS

GIS에서 주파수 특성을 갖는 이중 대역법에 의한 UHF 부분방전 측정기술

  • Published : 2006.03.01

Abstract

This Paper describes a dual bands PD measurement method which has two different bandwidths. The one bandwidth is 0.5 - 2 GHz and the other is 1 - 2GHz. This method is used for GIS diagnosis. In the experiment, it shows that the ratios between two PD quantities in dual bands depend on the defect types and gas pressures. The variations of ratios in different pressures are more sensitive than ones in defect types. And These ratios increase with increasing SF6 gas pressures. As these ratios give us additive information of PD we can analyze the defect type as well as risk assessment for the GIS reliably. Therefore the above result shows that these ratios are one of parameters for diagnosing GIS.

Keywords

References

  1. J. S. Pearson, B. F. Hampton and A. G. Sellars, 'A continuous UHF monitor for gas-insulated substation', IEEE trans Electrical Insulation Vol. 26 No. 3 June, 1991, pp 469 - 478 https://doi.org/10.1109/14.85119
  2. H. Okubo, T. Takahashi, T. Yamada and M. Hikita, 'Discrimination of streamer/leader type partial discharge in SF6 gas based discharge mechanism', Gaseous Dielectrics Vlll, Plenum Press, pp 269 - 274, 1998
  3. T. Utsumi, F. Endo, T. Ishikawa, S. Iwasa, T.Yamagiwa, ' Preventive maintenance ystem with a different gas injecting facility for GIS', IEEE Power Delivery Vol. 8, No.3 July 1993 pp 1107 - 1112 https://doi.org/10.1109/61.252597
  4. Sander Meijer, Andrea Bovis, Edward Gluski, John J. Smit and Alian Girodet, 'Analysis of the sensitivity of the UHF PD measuring technique', Conference Record of 2000 IEEE international Symposium on Electrical Insulation, April 2000, pp 395 - 399 https://doi.org/10.1109/ELINSL.2000.845533
  5. R. Feger, K. Feser, C. Neumann, V. Rees, 'Nonconventional UHF sensors for PD measurements on GIS of different design', Conference Record of 2000 IEEE international Symposium on Electrical Insulation, April 2000, pp 1395 - 1400 https://doi.org/10.1109/ICPST.2000.898173
  6. M. Knapp, R. Feger, K. Feser, 'Application of the CIGRE-Sensitivity verification for UHF PD detection in Three-Phase GIS', High Voltage Engineering Symposium, August 1999, 5
  7. H. Okubo, M. Yoshida, T. Takahashi, T. Hoshino, 'Partial discharge measurement in a long distance SF6 gas insulated transmission line(GIL)', IEEE Trans. Power Deliverly Vol.13, No.3 July 1998, pp. 683-690 https://doi.org/10.1109/61.686960
  8. T. Sakakibara, H. Murae, E. Haginomori, S. Wakabayashi, K. Emoto, A. Ogawa, 'Study of propagation phenomena of partial discharge pluses in gas insulated substation', IEEE Trans. on Power Delivery, Vol. 13, No.3 July 1998, pp768-776 https://doi.org/10.1109/61.686973
  9. Kwang Hwa Kim, Jae Gu Choi, Sang Hwa Yi, Jong Ho Sun, 'Measurement and Analysis of Partial Discharge by using Dual UHF Bands Method in GIS', Proceeding of 14th International Symposium on High Voltage Engineering. August 2005, pp. 384
  10. K. H. Kim, J. G. Choi, S. H. Lee and J. C. Kim, 'The characteristics of GIS partial discharges measured in two UHF bands', Proc. of 2003 J-K Sym, on electrical discharge & High Voltage Eng. November 2003, pp61-64